Yaskawa Electric America, Inc – www.yaskawa.com
IG.AFD.25, Page 1 of 6
Date: 10/7/09, Rev: 09-10
Modbus
®
TCP/IP Option Kit
CM090
This document applies to the Yaskawa F7U, G7U, P7U, E7U and G5M (Spec F) drives. For G5U(HHP) drives,
refer to IG.G5HHP.25.
Unpack the CM090 Modbus TCP/IP Option kit and verify that all components are present and undamaged.
CM090 Option Kit Parts List Qty.
Modbus TCP/IP Option Card 1
Shielded RJ-45 M-F Cable 1
Ground Wire 1
4”x1” Insulated Tubing 1
Cable Ties 2
Installation Guide (IG.AFD.25) 1
Connect power to the drive and verify that the drive functions correctly. This includes running the drive from the operator keypad. Refer to the appropriate drive technical
manual for information on connecting and operating the drive.
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be completely discharged.
Measure the DC bus voltage and verify that it is at a safe level.
Remove the operator keypad and drive cover.
Remove the operator keypad.
Remove the terminal and control covers.
Remove the option card hold-down by carefully compressing the top and bottom until it becomes free of its holder. Lift it out.
Mount the Modbus TCP/IP Option Card on the drive.
Connect the RJ-45 M-F cable supplied in the
CM090 kit to the Modbus TCP/IP Option Card.
Connect the ground cable supplied to ground
terminal J6 on the Modbus TCP/IP Option Card.
Align the J2 connector on the back of the Modbus
TCP/IP Option Card with its mating 2CN
connector on the drive control card.
Align the two standoffs on the front of the drive
control board with the two holes on the right side
of the Modbus TCP/IP Option Card.
Press the Modbus TCP/IP Option Card firmly
onto the drive 2CN connector and standoffs until
the J2 connector is fully seated on 2CN and the
drive standoffs have locked into their appropriate
holes.
Route the RJ-45 M-F cable and the ground cable
along the left-inside of the drive case.
Replace the option card hold down.
Connect the Modbus TCP/IP Option Card ground
wire to the ground terminal on the terminal
assembly.
Vue de la page 0
1 2 3 4 5 6

Résumé du contenu

Page 1 - TCP/IP Option Kit

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 1 of 6 Date: 10/7/09, Rev: 09-10 Modbus® TCP/IP Option KitCM090 This document applie

Page 2 - Date: 10/7/09, Rev: 09-10

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 2 of 6 Date: 10/7/09, Rev: 09-10  Apply power to the drive and verify that the dri

Page 3 - Subnet mask: 255.255.255.0

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 3 of 6 Date: 10/7/09, Rev: 09-10  Resetting the Modbus T

Page 4 - IG.AFD.25, Page 4 of 6

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 4 of 6 Date: 10/7/09, Rev: 09-10  Configure the Modbus TCP/IP Option Card.  Sele

Page 5 - IG.AFD.25, Page 5 of 6

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 5 of 6 Date: 10/7/09, Rev: 09-10  Finish the Modbus TCP/IP Option Card installation.

Page 6

Yaskawa Electric America, Inc – www.yaskawa.com IG.AFD.25, Page 6 of 6 Date: 10/7/09, Rev: 09-10 Modbus® TCP/IP Option KitCM090Copies of this Instal

Commentaires sur ces manuels

Pas de commentaire