Yaskawa iQpump Programming Manual Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Équipement Yaskawa iQpump Programming Manual. Yaskawa iQpump Programming Manual User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 210
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs

Résumé du contenu

Page 1 - Programming Manual

iQpump DriveProgramming ManualDocument Number: TM.iQp.02

Page 2

10 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ b1 SequenceThe Sequence Group contains parameters associated with starting and stopping the Dri

Page 3 - Warnings and Cautions

100 YASKAWA TM.iQp.02 iQpump Drive Programming Manual L2-04 Momentary Power Loss Voltage Recovery Ramp TimeSetting Range: 0.0 to 5.0 secFactory Defau

Page 4 - ◆ Intended Use

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 101◆ L3 Stall Prevention L3-01 Stall Prevention Selection During Accel L3-02 Stall Prevention Lev

Page 5 - Introduction

102 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 86 Figure 91 Time Chart for Stall Prevention During AccelerationThe L3-02 parameter

Page 6 - ◆ Software Versions

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 103 L3-05 Stall Prevention Selection During Running L3-06 Stall Prevention Level During RunningSe

Page 7 - Programming

104 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ L4 Speed Command Loss Detection L4-01 Speed Agreement Detection LevelSetting Range: 0.0 to 20

Page 8 - ◆ A1 Initialization

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 105◆ L5 Fault Restart L5-01 Number of Auto Restart AttemptsSetting Range: 0 to 10Factory Default:

Page 9 - A1-05 Select Password

106 YASKAWA TM.iQp.02 iQpump Drive Programming Manual• OL1 (Motor Overload)• OL3 (Overtorque)• OL2 (Drive Overload)• OV (DC Bus Overvoltage)• GF (Gro

Page 10 - ◆ b1 Sequence

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 107◆ L6 Torque Detection L6-01 Torque Detection Selection 1 L6-02 Torque Detection Level 1Setting

Page 11 - Figure 1.4

108 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 91 Figure 96 Over Torque DetectionFigure 1. 92 Figure 97 Under Torque DetectionOut

Page 12 - Figure 1. 5

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 109◆ L8 Hardware Protection L8-01 Internal Dynamic Braking Resistor Protection SelectionThis param

Page 13 - Figure 1.6

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 11Figure 1.3 Figure 3 Setpoint Potentiometer Connection DiagramRefer to Figure 4 for the connect

Page 14 - Feedback Device

110 YASKAWA TM.iQp.02 iQpump Drive Programming Manual L8-06 Input Phase Loss Detection Level Setting Range: 0.0 to 25.0% of Drives O V Trip pointFact

Page 15 - (CLOSED)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 111 L8-11 Heatsink Cooling Fan Operation Delay Time <0033>Setting Range: 0 to 300 secFactory

Page 16 - Time BrakeInjection DC

112 YASKAWA TM.iQp.02 iQpump Drive Programming Manual L8-18 Soft CLA SelectionThe Soft CLA (software current limit level) is an iQpump drive protecti

Page 17 - Waiting to RUN

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 113◆ n1 Hunting Prevention n1-01 Hunting Prevention Selection n1-02 Hunting Prevention Gain Setti

Page 18 - ◆ b2 DC Braking

114 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ o1 Monitor Configuration o1-01 User Monitor SelectionSetting Range: 6 to 94 Factory Default:

Page 19

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 115For example, if the iQpump drive needs to display the Elapsed Timer as the Power-On monitor, the

Page 20 - ◆ b3 Speed Search

116 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ o2 Key Selections o2-01 Local/Remote Key SelectionsThe o2-01 parameter will have no effect on

Page 21 - Search Delay Time (b3-05)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 117 o2-04 Drive / kVA SelectionSetting Range: 0 to FFFactory Default: Model DependentParameter o2-

Page 22 - Figure 1. 19

118 YASKAWA TM.iQp.02 iQpump Drive Programming Manual o2-05 Frequency Reference Setting Method SelectionThe factory default setting of the Frequency

Page 23

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 119 o2-10 Cumulative Cooling Fan Operation Time SettingSetting Range: 0 to 65535 HoursFactory Defa

Page 24 - ◆ b5 PI Function

12 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 5 Figure 5 Connection Diagram of PC or PLCIf you want the iQpump drive to receive the

Page 25 - Table 1 PI Setpoint Options

120 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ o3 Digital Operator Copy Function o3-01 Copy Function SelectionNote: The copy function is dis

Page 26 - No Integral With Integral

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 121A successful COPY of the parameter values will display:An error may occur while writing the para

Page 27 - T = b5-14

122 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ P1 Pump Basic P1-01 Pump Mode Lead-Lag OperationThe iQpump drive can be configured to specify

Page 28 - Factory Default: 0.0 sec

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 123Figure 1.96 Figure 101 Note: When the Fixed Speed Auto is activated, the sleep and lead-lag fu

Page 29 - ◆ b8 Energy Savings

124 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P1-02 System UnitsThe iQpump drive can be configured to program the drive using units or scalin

Page 30 - ◆ C1 Accel/Decel

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 125 P1-04 Start LevelSetting Range: 0.0 to 6000.0Factory Default: 0.0The iQpump drive can be confi

Page 31 - Frequency

126 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P1-09 High Feedback LevelSetting Range: 0.0 to 6000.0 Factory Default: 155.0 (system units P1-0

Page 32 - C2 S-Curve Acc

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 127 P1-12 Not Maintaining Setpoint and Loss of Prime Time <0032>Setting Range: 0 to 3600 sec

Page 33 - ◆ C4 Torque Comp

128 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 98 Figure 103 Loss of Prime (LOP) P1-15 Low Water InputThe iQpump drive can be confi

Page 34 - ◆ C6 Carrier Frequency

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 129◆ P2 Pump Protection P2-01 Sleep Level TypeIf P2-01 = “0: Output Frequency”The iQpump drive can

Page 35 - Carrier Frequency Limits

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 13Figure 1.6 Figure 6 Connection Diagram of External Start/Stop SwitchIf the Run command is dete

Page 36 - Setpoint References

130 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 99 Figure 104 Sleep Function Based on Output FrequencyIf P2-01 = “1: Output Current”

Page 37

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 131Figure 1.1 00 Figure 105 Sleep Function Based on Output CurrentIf P2-01 = “2: Feedback”The iQp

Page 38 - Operating

132 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 1 Figure 106 Sleep Function Based on Feedback LevelSleep Delay TimeP2-03

Page 39 - Jump Frequencies

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 133 P2-02 Sleep LevelSetting Range: 0.0 to 6000.0Factory Default: 0.0The iQpump drive can be confi

Page 40 - ◆ E1 V/f Pattern

134 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 2 Figure 107 No-Flow Detection During Deceleration P2-05 Feedback Detection Drop T

Page 41 - E1-05 Maximum Output Voltage

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 135The iQpump drive can be configured to allow a maximum number of cycles before initiating a “Pump

Page 42

136 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 3 Figure 108 Total setpoint compensation can be monitored with Total Setpoint Comp

Page 43

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 137The programming of the No-Flow Activation Level (P2-11) will activate the no-flow detection func

Page 44

138 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 5 Figure 110 Note: Sleep function P2-02 is enable (P2-02 > 0)

Page 45 - ◆ E2 Motor Setup

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 139 P2-12 No-Flow Detection BandwidthSetting Range: 0 to 1000 RPMFactory Default: 15 RPMThe iQpum

Page 46 - ◆ F6 Com OPT Setup

14 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Feedback DeviceThe iQpump Controller requires a feedback device (e.g. Pressure transducer, flow

Page 47 - ◆ H1 Digital Inputs

140 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P2-16 No-Flow Setpoint CompensationSetting Range: 0.0 to 6000.0Factory Default: 1.5The iQpump d

Page 48 - Figure 1. 33

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 141 P2-20 Alternative Sleep Activation LevelSetting Range: 0.0 to 120.0 HzFactory Default: 0.0 HzT

Page 49

142 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 8 Figure 113 The sleep function can be active during the following conditions:• Whe

Page 50 - Figure 1. 35

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 143◆ P3 Pump Protection P3-01 Lead-Lag ControlThe iQpump drive can be configured for lead-lag cont

Page 51

144 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.10 9 Figure 114 Auxiliary Pump De-Staging (OFF)The de-staging of the auxiliary pumps

Page 52 - Accelerates to

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 145Figure 1.110 Figure 115 The pump system can be allowed to stabilize by programming a time into

Page 53 - Figure 1.39

146 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.111 Figure 116 Auxiliary Pump De-Staging (OFF)The de-staging of the auxiliary pumps 2

Page 54

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 147Figure 1.112 Figure 117 The pump system can be allowed to stabilize by programming a time into

Page 55 - Figure 1.40

148 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 113 Figure 118 Auxiliary Pump De-Staging (OFF)The de-staging of the auxiliary pumps

Page 56

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 149Figure 1.114 Figure 119 P3-02 Drive Multi/Maximum LevelSetting Range: 0.0 to 120.0 HzFactory

Page 57 - Table 15 6C, COM/INV SEL 2

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 15To issue the Run command via a network option card: Set b1-02 = “3: Option PCB,” and plug a netwo

Page 58 - Figure 1. 43

150 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P3-03 Add Pump Delta LevelSetting Range: 0.0 to 6000.0Factory Default: 0.0The delta level used

Page 59

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 151If P3-01 = 2: Output Frequency + Feedback LevelThe de-staging (turning OFF) of the auxiliary pum

Page 60 - (Thermostat FltNo)

152 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 115 Figure 120 P3-08 Multi Pump Setpoint DecreaseSetting Range: 0.0 to 6000.0 Fact

Page 61 - (Low Water Level)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 153Figure 1.116 Figure 121 P3-09 Pump 2 Frequency Shutdown LevelSetting Range: 0.0 to 120.0 HzF

Page 62 - (Thermostat FltNC)

154 YASKAWA TM.iQp.02 iQpump Drive Programming ManualIf P3-01 = 1: Feedback Level (P3-02: Not Used)The Pump 3 Frequency Shutdown Level (P3-10) is not

Page 63 - ◆ H2 Digital Outputs

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 155Figure 1.117 Figure 122 P3-12 Delta Setpoint Feedback Acc/Dec ChangeoverSetting Range: 0.0 t

Page 64 - Figure 1. 53

156 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P3-13 Friction Compensation Start FrequencySetting Range: 0.0 to 120.0 HzFactory Default: 0.0 H

Page 65

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 157Figure 1.119 Figure 124 The maximum compensation at Maximum Output Frequency (E1-04) is specif

Page 66 - Function: Fault (Setting: E)

158 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ P4 Pump Protection P4-01 Pre-Charge LevelSetting Range: 0.0 to 6000.0 Factory Default: 0.0 Th

Page 67 - OFF (Open)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 159Figure 1.1 20 Figure 125 Figure 1.1 21 Figure 126 TIMEFeedbackMulti-function Input #840 HzPr

Page 68 - Figure 1. 59

16 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 10 Figure 10 Coast to StopImportant: After a stop is initiated, a subsequent Run comm

Page 69

160 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.12 2 Figure 127 Figure 1.12 3 Figure 128 TIMETimer ExpiredMulti-function Input #840

Page 70 - ◆ H3 Analog Inputs

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 161Pre-Charge with Thrust Bearing Function Both Enabled. <0032>When both Pre-Charge and Thrus

Page 71 - Analog Input Signal

162 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1.12 5 Figure 130 RunCommand Output Frequency Pre-Charge Frequency P4-0

Page 72 - Table 17 DIP Switch S1

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 163Figure 1.1 26 Figure 131 P4-02 Pre-Charge FrequencySetting Range: 0.0 to 120.0 HzFactory Def

Page 73 - Command

164 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P4-03 Pre-Charge TimeSetting Range: 0.0 to 3600.0 minFactory Default: 0.0 minThe iQpump drive c

Page 74 - Rbranch =

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 165 P4-05 Thrust Bearing FrequencySetting Range: 0.0 to 120.0 HzFactory Default: 0.0 HzThe iQpump

Page 75

166 YASKAWA TM.iQp.02 iQpump Drive Programming Manual P4-06 Thrust Bearing Deceleration Time <0032>Setting Range: 0.0 to 6000.0 secFactory Defa

Page 76 - (Filtered)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 167 P4-09 Loss of Prime Maximum Restart Time After Restart <0032>Setting Range: 0.2 to 6000.

Page 77 - ◆ H4 Analog Outputs

168 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ P5 Pump Protection P5-01 Hand Mode ReferenceThe iQpump drive can be operated manually or in t

Page 78 - limits are

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 169Connection Diagram of External SignalFigure 1.1 31 Figure 136 P5-02 Hand ReferenceSetting Ra

Page 79 - Analog Input

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 17Figure 1.12 Figure 12 Coast to Stop with Timer b1-08 Run Command Selection During ProgrammingA

Page 80

170 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ Pump Tuning PI Control Tuning (b5 Group)The built-in PI controller in the iQpump is used to c

Page 81 - ◆ Using Modbus Communication

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 171Figure 1.1 32 Figure 137 PI Feedback Response CharacteristicsThe iQpump offers programmable ac

Page 82 - Figure 1. 78

172 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ T1 Auto-Tuning T1-02 Motor Rated PowerSetting Range: 0.00 to 650.00 kWFactory Default: Model

Page 83

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 173Appendix: AParametersThis appendix lists all the parameter numbers and names, along with a descr

Page 84 - Message Format

174 YASKAWA TM.iQp.02 iQpump Drive Programming ManualParameter ListTable 1 Parameter ListParameter No.Modbus AddressParameter NameDigital Operator

Page 85 - Modbus Function Code Details

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 175b2-03 018BHDC Injection Braking Time at StartDCInj Time @ StartSets the time length of DC injec

Page 86 - ◆ Loopback Test (08H)

176 YASKAWA TM.iQp.02 iQpump Drive Programming Manualb5-0701ABHPI Offset AdjustmentPI OffsetSets the amount of offset of the output of the PI contr

Page 87

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 177C1-11 020AHAccel/Decel Switch FrequencyAcc/Dec SW FreqSets the frequency for automatic switchin

Page 88 - Modbus Data Tables

178 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Preset Referenced1-010280HSetpoint Reference 1Setpoint 1Digital preset setpoint reference 1.

Page 89 - Monitor Data

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 179E1-04 0303HMaximum Output FrequencyMax FrequencyTo set V/f characteristics in a straight line,

Page 90

18 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ b2 DC BrakingThe DC Braking Group contains parameters associated with the DC injection braking

Page 91 - Enter Command

180 YASKAWA TM.iQp.02 iQpump Drive Programming ManualF6-03 03A4HStopping Method for External Fault from Communication Option CardEF0 Fault Action0:

Page 92 - Slave Not Responding

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 181H1-04 0403HTerminal S6 Function SelectionTerminal S6 Sel20: External Pump Fault, Normally Open,

Page 93 - ◆ Modbus Self-Diagnosis

182 YASKAWA TM.iQp.02 iQpump Drive Programming ManualH1-050404HTerminal S7 Function SelectionTerminal S7 Sel 83: Thermostat Fault,Function Active in

Page 94 - H5-07 RTS Control Selection

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 183Parameter No.Modbus AddressParameter NameDigital Operator DisplayDescriptionSetting RangeFactor

Page 95 - Factory Default: 2.0 sec

184 YASKAWA TM.iQp.02 iQpump Drive Programming ManualH2-02(continued)040CHTerminal M3-M4 Function SelectionTer m M3 -M 4 Se l42: Pump FaultFunction

Page 96 - ◆ L1 Motor Overload

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 185H4-04 0420HTerminal AM Monitor SelectionTer minal AM Se lSelects which monitor will be output

Page 97 - (Percent of motor FLA)

186 YASKAWA TM.iQp.02 iQpump Drive Programming ManualH5-09 0435HCommunication Error Detection TimeCE Detect TimeDetermines how long communications m

Page 98 - (0-10 Vdc)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 187L3-04 0492HStall Prevention Selection During DecelStallP Decel Sel0: Disabled (The Drive decele

Page 99

188 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Torque DetectionL6-01 04A1HTorque Detection Selection 1Load DetectionDetermines the Drive&apos

Page 100

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 189L8-12 04B8HAmbient Temperature SettingAmbient TempWhen the Drive is installed in an ambient tem

Page 101 - ◆ L3 Stall Prevention

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 19Parameter b2-04 also serves the function of affecting the length of time DC Injection to stop (b1

Page 102 - Figure 1. 87

190 YASKAWA TM.iQp.02 iQpump Drive Programming Manualo1-07 0518HSecond Line User Monitor Selection2nd Monitor SelSets the “U1” monitor always displa

Page 103

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 191o3-02 0516HRead Allowed Selection Read AllowableEnables and disables all digital operator copy

Page 104 - Figure 1. 89

192 YASKAWA TM.iQp.02 iQpump Drive Programming ManualP1-11<0032>0106HMaximum SetPoint DifferenceMax Setpoint DiffWhen the Drive is running an

Page 105

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 193P2-08 0611HOver Cycling ModeOver Cycle ModeSets the Over Cycle Mode:0: Disabled1: Alarm2: Pump

Page 106

194 YASKAWA TM.iQp.02 iQpump Drive Programming ManualP3-020615HDrive Multi/Maximum LevelMax-Multi LevelSets the maximum level used for multiplex pu

Page 107 - ◆ L6 Torque Detection

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 195P3-09061CHPump 2 Frequency Shutdown LevelP2 Freq. Shd LvlSets the level used for multiplex pum

Page 108 - Figure 1. 92

196 YASKAWA TM.iQp.02 iQpump Drive Programming ManualPump AdvancedP4-010115HPre-Charge LevelPre-Charge LevelSets the level when the drive will run

Page 109

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 197P4-08<0032>011CHProtection Fault Auto Restart EnableProt Flt RestrtSetting to enable / di

Page 110

198 YASKAWA TM.iQp.02 iQpump Drive Programming ManualMonitor ListTable 2 Monitor ListParameter No.Modbus AddressParameter Name Digital Operator Dis

Page 111 - 0 Disabled

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 199U1-16 004FHTerminal A2 Input Voltage Ter m A2 le ve lDisplays the input current (or voltage) o

Page 112 - L8-18 Soft CLA Selection

2 YASKAWA TM.iQp.02 iQpump Drive Programming Manual ◆ Quick Reference for iQpump (P7U) <0033>* Factory setting changes to “B” when b5-01=1.** F

Page 113 - ◆ n1 Hunting Prevention

20 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ b3 Speed SearchThe Speed Search function allows the iQpump drive to determine the speed of a mo

Page 114 - ◆ o1 Monitor Configuration

200 YASKAWA TM.iQp.02 iQpump Drive Programming ManualU1-93 723HTotal Setpoint CompensationTotal SP Comp.Displays total absolute setpoint compensation

Page 115 - U1-24= 64.55%

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 201Fault Trace ListTable 3 Fault Trace ListParameter No.Modbus AddressFault TraceU2-01 0080HCurre

Page 116 - ◆ o2 Key Selections

202 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFault History ListTable 4 Fault History ListParameter No.Modbus AddressFault HistoryU3-01 0090

Page 117

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 203Table 5 Decimal to Hex ConversionDecimal Hex Decimal Hex1 1 51 332 2 52 343 3 53 354 4 54 365

Page 118 - U1-13 = 0H

204 YASKAWA TM.iQp.02 iQpump Drive Programming ManualTHIS PAGE INTENTIONALLY LEFT BLANK.

Page 119 - U1-40 = 152H

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 205Appendix: BFactory Default SettingsThis appendix lists the factory default settings for the param

Page 120

206 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFactory Default SettingsThe following tables detail the factory default settings for the paramete

Page 121 - VERIFY ERROR

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 207Table 36 480 VAC Drives Drive ModelCIMR-P7U--107Nominal HpFactory Defaultforb8-04Factory Defau

Page 122 - ◆ P1 Pump Basic

208 YASKAWA TM.iQp.02 iQpump Drive Programming ManualTHIS PAGE INTENTIONALLY LEFT BLANK.

Page 123 - Frequency Detection 2

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 209THIS PAGE INTENTIONALLY LEFT BLANK.

Page 124 - P1-03 Feedback Device Scaling

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 21Figure 1.16 Figure 16 Speed Search (Estimated Speed Method) after momentary power loss where th

Page 125 - P1-07 Low Feedback Level

iQpump DriveYASKAWA ELECTRIC AMERICA, INC.Drives Division 16555 W. Ryerson Rd., New Berlin, WI 53151, U.S.A.Phone: (800) YASKAWA (800-927-5292) Fa

Page 126 - P1-09 High Feedback Level

22 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 19 Figure 19 Speed Search (Current Detection Method) after momentary power loss where

Page 127 - P1-14 Prime Loss Level

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 23◆ b4 Delay TimersThe iQpump drive has an internal timer function that operates independently from

Page 128 - P1-15 Low Water Input

24 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ b5 PI FunctionThe capability to accept an analog signal as feedback for a PI (Proportional + In

Page 129 - ◆ P2 Pump Protection

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 25Table 1 PI Setpoint OptionsIn some situations there are two feedback inputs. The drive can be pr

Page 130

26 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 22 Figure 22 PI Feedback Response Characteristics b5-04 Integral Limit SettingSettin

Page 131 - START DELAY

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 27 b5-09 PI Output Level SelectionNormally, the output of the PI function causes an increase in mo

Page 132 - Sleep Delay Time

28 YASKAWA TM.iQp.02 iQpump Drive Programming Manual b5-17 PI Accel/Decel TimeSetting Range: 0.0 to 25.5 secFactory Default: 0.0 secThis is a soft st

Page 133 - P2-03 Sleep Delay Time

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 29◆ b8 Energy Savings The energy savings function improves overall system operating efficiency by o

Page 134 - Figure 1.10 2

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 3Warnings and CautionsThis Section provides warnings and cautions pertinent to this product, that if

Page 135

30 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ C1 Accel/Decel Acceleration TimesSetting Range: 0.0 to 6000.0 secFactory Defaults: C1-01 and C

Page 136 - P2-09 Setpoint Compensation

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 31Figure 1.24 Figure 24 Accel/Decel Switch Frequency Operation Output Frequency Time C1-11C1-03 R

Page 137 - P2-17 No Flow

32 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ C2 S-Curve Acc S-Curve CharacteristicsSetting Range: 0.00 to 2.50 secFactory Default: 0.20 sec

Page 138 - Figure 110

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 33◆ C4 Torque Comp C4-01 Torque Compensation GainSetting Range: 0.00 to 2.50 Factory Default: 1.00

Page 139 - P2-13 No-Flow Detection Time

34 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ C6 Carrier Frequency C6-01 Normal Duty SelectionAdjustment of parameter C6-01 will affect the

Page 140 - 1 Inside Bandwidth (P2-15)

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 35 Carrier Frequency LimitsSetting Range: 0.4 to 10.0 kHzFactory Default: Model Dependent C6-05 C

Page 141 - SLEEP PERMITTED

36 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ d1 Setpoint and Jog References Setpoint ReferencesSetting Range: 0 to P1-03 ValueFactory Defau

Page 142

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 37 d1-17 Jog Frequency Reference (LCD Operator Function Only JVOP-160)Setting Range: 0.00 to E1-04

Page 143 - ◆ P3 Pump Protection

38 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ d2 Reference (Speed Command) Limits d2-01 Frequency Reference Upper LimitSetting Range: 0.0 to

Page 144 - Figure 1.10 9

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 39◆ d3 Jump Frequencies Jump FrequenciesSetting Range: 0.0 to 200.0 HzFactory Default: 0.0 Hz d3-

Page 145

4 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ Intended UseDrives are intended for installation in electrical systems or machinery.For use in t

Page 146 - Output #40

40 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ E1 V/f Pattern E1-01 Input Voltage SettingSetting Ranges: 155.0 V to 255.0 V (208 V/240 V Mode

Page 147 - Figure 1.112

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 41Table 4 Preset V/f PatternsIf one of the custom V/f patterns is selected, then parameters E1-04

Page 148

42 YASKAWA TM.iQp.02 iQpump Drive Programming Manual E1-06 Base FrequencySetting Range: 0.0 to 120.0 HzFactory Default: 60.0 Hz E1-07 Mid Output Fre

Page 149 - Shutdown Pump Delta Level

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 43Figure 1.31 Figure 31 Custom V/f Pattern Programming CurveIncreasing the voltage in the V/f pat

Page 150 - P3-04 Add Pump Delay Time

44 YASKAWA TM.iQp.02 iQpump Drive Programming ManualTable 7 V/f Pattern Default Settings for Drive Capacity 50 to 150 HP for 240 V Class Parameter

Page 151

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 45◆ E2 Motor Setup E2-01 Motor Rated CurrentSetting Range: 10% to 200%Factory Default: Model Depen

Page 152 - Figure 1. 115

46 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ F6 Com OPT Setup F6-01 Operation Selection After Communication ErrorIf a serial communication

Page 153

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 47◆ H1 Digital Inputs Terminal Function SelectionsSetting Range: 0 to 86Factory Defaults: H1-01 =

Page 154

48 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: 3-Wire Control (Setting: 0)When one of the digital inputs is programmed for 3-Wire cont

Page 155 - Figure 1.117

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 49Function: Multi-step SP1 (Setting: 3)Function: Multi-step SP2 (Setting: 4)The iQpump drive can be

Page 156

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 5IntroductionThis Section describes the applicability of the ManualThe iQpump (P7U) is a Pulse Width

Page 157 - Figure 1.119

50 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Ext Baseblk N.O. (Setting: 8)Function: Ext Baseblk N.C. (Setting: 9)When the iQpump dri

Page 158

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 51Function: Acc/Dec RampHold (Setting: A)The Acc/Dec RampHold function will clamp (“hold”) the spee

Page 159 - Figure 126

52 YASKAWA TM.iQp.02 iQpump Drive Programming ManualImportant: Be sure to set b1-01 = “1: Terminals,” (Auto Setpoint =Terminals) if the MOP function

Page 160 - Figure 128

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 53Function: Fast Stop N.O. (Setting: 15)Function: Fast Stop N.C. (Setting: 17)The Fast Stop functio

Page 161 - <0032>

54 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: External Fault (Setting: 20 through 2F)External Fault functionality can be programmed i

Page 162 - Figure 130

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 55Function: PI SFS Cancel (Setting: 34)SFS means softstart, also referred to as accel/decel in this

Page 163 - P4-02 Pre-Charge Frequency

56 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Motor Pre-heat (Setting: 60)In order to prevent condensation on the motor windings, a D

Page 164 - P4-03 Pre-Charge Time

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 574. Turn On the terminating resistance (Move Switch 1 of Dip Switch 1 to the ON position).Figure 1

Page 165 - Figure 1.1 28

58 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Hand Mode (Setting: 80)A digital input can be configured to operate the drive in the ha

Page 166

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 59Figure 1.44 Figure 44 Wiring DiagramFigure 1.45 Figure 45 Timing ChartTIMEOutput FrequencySle

Page 167 - (factory default)

6 YASKAWA TM.iQp.02 iQpump Drive Programming Manual0.1 Conventions Used in this Manual◆ Software VersionsYaskawa recognizes the need to continuously

Page 168 - ◆ P5 Pump Protection

60 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Thermostat Fault (Setting: 83)A digital input can be configured to indicate a Thermosta

Page 169 - P5-02 Hand Reference

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 61Function: Low Water Level (Setting: 85)A digital input can be configured to indicate a Low Water

Page 170 - ◆ Pump Tuning

62 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Thermostat Fault (Setting:87) <0032>A digital input can be configured to indicate

Page 171 - 25.0 Seconds

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 63◆ H2 Digital Outputs Terminal Function SelectionsSetting Range: 0 to 42Factory Defaults: H2-01 =

Page 172 - ◆ T1 Auto-Tuning

64 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Fref/Set Agree 1 (Setting: 3)The “Fref/Set Agree 1” output will close whenever the actua

Page 173 - Appendix: A

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 65Function: Freq Detect 2 (Setting: 5)A Freq Detect 2 output will be closed whenever the output fre

Page 174 - Parameter List

66 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Trq Det 1 N.O. (Setting: B)The Trq Det 1 function ties a digital output to the overtorq

Page 175 - PI Control

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 67Function: Reset Cmd Active (Setting: 11)A Reset Cmd Active digital output will close to signal th

Page 176 - Accel / Decel

68 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Overload (OL1) Alarm (Setting: 1F)The OL1 fault function is designed to protect the mot

Page 177 - Carrier Freq

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 69Function: Pump 3 Control (Setting: 41)The multi-function digital output is configured to enable a

Page 178 - Jump Frequencies

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 71ProgrammingThis Manual contains descriptions of all user accessible parameters contained in the Dr

Page 179 - Com OPT Setup

70 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ H3 Analog Inputs H3-02 Terminal A1 Gain SettingSetting Range: 0.0 to 1000.0%Factory Default: 1

Page 180 - Digital Inputs

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 71Figure 1.63 Figure 63 Output Frequency with Reduced Bias SettingAs a further example, for an in

Page 181

72 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 65 Figure 1. 66 Figure 65 DIP Switch S1Table 17 DIP Switch S1 H3-09 Terminal A2 F

Page 182

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 73Figure 1.67 Figure 66 Effect of Frequency Bias Function on Speed CommandIt should be noted that

Page 183 - Digital Outputs

74 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 69 Figure 68 Frequency Bias 2 Applied to Analog Speed CommandFunction: Motor Temperat

Page 184 - Analog Outputs

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 75After the connections are made, configure the A2 analog input for motor temperature protection by

Page 185 - Serial Com Setup

76 YASKAWA TM.iQp.02 iQpump Drive Programming Manual H3-10 Terminal A2 Gain SettingSetting Range: 0.0 to 1000.0%Factory Default: 100.0% H3-11 Termin

Page 186 - Stall Prevention

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 77◆ H4 Analog Outputs H4-01 Terminal FM Monitor SelectionSetting Range: 1 to 53Factory Default: 2:

Page 187 - Fault Restart

78 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFunction: Output kWatts (Setting: 8)The analog output level will correspond to an internally calc

Page 188 - Hdwe Protection

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 79The gain and bias parameters for the analog outputs of the iQpump drive allow the programmer to c

Page 189 - Monitor Select

8 YASKAWA TM.iQp.02 iQpump Drive Programming ManualiQpump Basic Programming ParametersThe initialization group contains parameters associated with ini

Page 190 - COPY Function

80 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Terminal Signal Level SelectionsWhen the iQpump drive is equipped with the optional, removable

Page 191 - Pump Basic

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 81◆ H5 Serial Communications SetupThis section explains the individual functions used in special ap

Page 192 - Pump Protection

82 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 77 Figure 77 Communication Connection Terminals and Terminating ResistanceImportant:•

Page 193 - Pump Multiplex

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 83 Related ParametersThe following parameters need to be set correctly to insure proper operation

Page 194

84 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Message FormatIn Modbus communication, the master sends commands to the slave, and the slave res

Page 195

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 85Modbus Function Code Details◆ Reading/Holding Register Contents (03H)Read the contents of the sto

Page 196 - Pump Advanced

86 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ Loopback Test (08H)The loopback test returns the command message directly as the response messa

Page 197 - Auto-Tuning

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 87◆ Write In Several Holding Registers (10H)Write the specified data to the desired slave indicatin

Page 198 - Monitor List

88 YASKAWA TM.iQp.02 iQpump Drive Programming ManualModbus Data TablesThe data tables are shown below. The types of data are as follows: Reference da

Page 199

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 89 Monitor DataThe following table shows the monitor data. Monitor data can only be read.Table 23

Page 200 - Motor Speed

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 9Important: Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The follo

Page 201 - Fault Trace List

90 YASKAWA TM.iQp.02 iQpump Drive Programming Manual002BHSequence input statusBit 0 Input terminal S1 1: ON 0: OFFBit 1 Input terminal S2 1: ON 0: OF

Page 202 - Fault History List

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 91 Broadcast DataThe following table shows the broadcast data. Broadcast Data Can Be Written (fuNc

Page 203

92 YASKAWA TM.iQp.02 iQpump Drive Programming Manual Error CodesThe following table shows Modbus communication error codes.Table 26 Error Codes Sl

Page 204

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 93◆ Modbus Self-DiagnosisThe iQpump drive has a built-in function for self-diagnosing the operation

Page 205 - Appendix: B

94 YASKAWA TM.iQp.02 iQpump Drive Programming ManualIt may be necessary to avoid the 19.2 K baud setting if frequent serial communications errors occ

Page 206 - Factory Default Settings

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 95 H5-09 Communication Error Detection TimeSetting Range: 0.0 to 10.0 secFactory Default: 2.0 secT

Page 207 - Table 36 480 VAC Drives

96 YASKAWA TM.iQp.02 iQpump Drive Programming Manual◆ L1 Motor Overload L1-01 Motor Overload Protection SelectionThe iQpump drive has an I2t electro

Page 208

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 97Figure 1.82 Figure 87 Motor Overload Protection Time based on Output frequency and Load L1-03

Page 209

98 YASKAWA TM.iQp.02 iQpump Drive Programming ManualFigure 1. 83 Figure 88 A typical PTC Thermistor characteristic shown on the following page.Figu

Page 210

YASKAWA TM.iQp.02 iQpump Drive Programming Manual 99◆ L2 Momentary Power Loss Ride-thru FunctionWhen momentary power loss recovery is enabled (L2-01≠

Commentaires sur ces manuels

Pas de commentaire