3-12
!External Fault Setting Procedure
Examples of the Digital Operator displays that appear when setting an eternal fault for a multi-function
contact input in Advanced Programming Mode are shown in the following diagram.
Fig 3.5 External Fault Function Setting Example
** Main Menu **
-DRIVE-
Operation
** Main Menu **
-QUICK-
Quick Setting
** Main Menu **
-ADV-
Programming
** Main Menu **
-VERIFY-
Modified Consts
** Main Menu **
-A.TUNE-
Auto-Tuning
MENU
Digital Inputs
-ADV-
H1-01=24
Terminal S3 Sel
MENU
MENU
MENU
MENU
ESC
DATA
ENTER
Terminal S3 Sel
-ADV-
H1- 01 =24
External Fault
ESC
ESC
DATA
ENTER
RESET
Monitor Display Setting DisplayMode Selection Display
*24*
1
2
A
B
A
B
Digital Inputs
-ADV-
H2-01= 0
Term M1-M2 Sel
Pulse I/O Setup
-ADV-
H6-01= 0
Pulse Input Sel
Terminal S4 Sel
-ADV-
H1- 02 =14
*14*
Terminal S8 Sel
-ADV-
H1- 08 =08
Ext BaseBlk N.O.
*08*
Terminal S3 Sel
-ADV-
H1- 01= 24
NO/Always Det
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 25
NC/Always Det
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 26
NO/During RUN
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 27
NC/During RUN
*24*
Coast to Stop
Terminal S3 Sel
-ADV-
H1- 01= 2F
NC/During RUN
*24*
Alarm Only
3
4
3
4
1
2
DATA
ENTER
Fault Reset
Terminal S4 Sel
-ADV-
H1-02 =14
Digital Inputs
ESC
RESET
"24"
"14"
"08"
Terminal S8 Sel
-ADV-
H1-08 =08
Digital Inputs
ESC
RESET