8 APPENDIX
8.1 List of Command Code Registers
8.1.1 Command Data (Read and Write)
Command Code Description Drive
Read Write BIT F7 G7
1000H - Reserved Complete Yes Yes
Run Cmd Yes Yes
0 Forward / Stop Command 1: Run 0: Stop Yes Yes
1 Reverse / Stop Command 1: Run 0: Stop Yes Yes
2 External Fault 1: Fault (EF0) Yes Yes
3 Fault Reset 1: Reset Command Yes Yes
4 Comnet Yes Yes
5 Comctrl Yes Yes
6 Multi-Function Input Command 3 (Terminal S3) Yes Yes
7 Multi-Function Input Command 4 (Terminal S4) Yes Yes
8 Multi-Function Input Command 5 (Terminal S5) Yes Yes
9 Multi-Function Input Command 6 (Terminal S6) Yes Yes
A Multi-Function Input Command 7 (Terminal S7) Yes Yes
B Multi-Function Input Command 8 (Terminal S8) No Yes
C Multi-Function Input Command 9 (Terminal S9) No Yes
D Multi-Function Input Command 10 (Terminal S10) No Yes
E Multi-Function Input Command 11 (Terminal S11) No Yes
1001H -
F Multi-Function Input Command 12 (Terminal S12) - -
1002H - Frequency Reference (set the units displayed with parameter o1-03) Yes Yes
1003H
-
Not Used - -
1004H
- Not Used No Yes
1005H
- Not Used No Yes
1006H
- PID Desired Value Yes Yes
1007H - Analog Output 1 Setting (-11V/-1540~11V/1540: Enabled when H4-01 is set to “31”) Yes Yes
1008H - Analog Output 2 Setting (-11V/-1540~11V/1540: Enabled when H4-04 is set to “31”) Yes Yes
Multi-Function Output Setting Yes Yes
0 Relay Output (Terminal M1-M2) 1: ON 0: OFF Yes Yes
1 PHC1 (Terminal P1-PC) 1: ON 0: OFF Yes Yes
2 PHC2 (Terminal P2-PC) 1: ON 0: OFF Yes Yes
3 PHC3 (Terminal P3-C3) 1: ON 0: OFF No Yes
4 PHC4 (Terminal P4-C4) 1: ON 0: OFF No Yes
5 Not Used
-
-
6 Fault Relay (Terminal MA-MC) Output. Determined by bit-7: 1: ON, 0:
OFF.
Yes Yes
7 Fault Relay (Terminal MA-MC) 1: ON 0: OFF Yes Yes
1009H -
8-F Not Used Yes Yes
100AH-
100EH
200AH
-
200EH
Not Used - -
Command Selection Setting Yes Yes
0 Not Used Yes Yes
1 PID Desired Value Input 1: Enabled 0: Disabled Yes Yes
2-B Not Used Yes Yes
C 1: Batch Data Transfer Terminal S5 Input 1: Enabled 0: Disabled Yes Yes
D 1: Batch Data Transfer Terminal S6 Input 1: Enabled 0: Disabled Yes Yes
E 1: Batch Data Transfer Terminal S7 Input 1: Enabled 0: Disabled Yes Yes
100FH -
F Not Used - -
NOTE: Any bit that is not used will be written as “0” when saving data to the Command Code.