YASKAWA J1000
Specifications
Specifications
Control Characteristics
Control methods V/f Control
Frequency Control Range 0.01 to 400 Hz
Frequency Accuracy
(Temperature Fluctuation)
Digital input: within ±0.01% of the max. output frequency (−10°C to +50°C)
Analog input: within ±0.5% of the max. output frequency (25°C ±10°C)
Frequency Setting
Resolution
Digital input: 0.01 Hz
Analog input: 1/1000 of max. frequency
Output Frequency Resolution 1/2
20
x Maximum output frequency (E1–04)
Frequency Setting Signal Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to 20 mA (250 Ω)
Starting Torque 150% / 3 Hz
Speed Control Range 1:20
Accel/Decel Time 0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Braking Torque
q Short-time decel torque*
1
: over 150% for 0.1/0.2 kW motors, over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors, and over 20% for 2.2 kW and above motors.
w Continuous regen. torque: approx. 20% (approx. 125% with dynamic braking resistor option*
2
: 10% ED, 10 s, internal braking transistor)
V/f Characteristics User-selected programs, V/f preset patterns possible
Main Control
Functions
Momentary power loss ride-thru, Speed search, 9-step speed (max), Accel/decel time switch, S-curve accel/decel, 3-wire sequence, Cooling fan on/off switch, Slip compensation, Torque
compensation, Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, Overexcitation braking, Fault restart ...
Protection Function
Motor Protection Motor overheat protection based on output current
Momentary Overcurrent Protection Drive stops when output current exceeds 200% of Heavy Duty Rating
Overload Protection Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)*
3
Overvoltage Protection
200 V class: Stops when DC bus exceeds approx. 410 V
400 V class: Stops when DC bus exceeds approx. 820 V
Undervoltage Protection
Stops when DC bus voltage falls below the following levels:
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350 V (3-phase 380 V)
Momentary Power Loss Ride-Thru Stops after approx. 15 ms (default).
Heatsink Overheat Protection Protection by thermistor
Braking Resistance Overheat Protection Overheat protection for braking resistor (optional ERF-type, 3% ED)
Stall Prevention Separate settings allowed during acceleration and during run. Enable/disable only during deceleration.
Ground Fault Protection Protection by electronic circuit *
4
Charge LED Charge LED remains lit until DC bus falls below approx. 50 V
Operating Environment
Area of Use Indoors
Ambient Temperature -10 to +50°C (IP20 open chassis), -10 to +40°C (NEMA Type 1)
Humidity 95 RH% or less (no condensation)
Storage Temperature -20 to +60°C (short-term temperature during transportation)
Altitude Max. 1000 m (output derating of 1% per 100 m above 1000 m, max. 3000 m)
Shock 10 to 20 Hz (9.8 m/s
2
) max., 20 to 55 Hz (5.9 m/s
2
) max.
Safety Standard UL508C
Protection Design IP20 open-chassis, NEMA Type 1 enclosure (option)
*
1
Momentary average deceleration torque refers to the deceleration torque from 60Hz down to 0 Hz. This may vary depending on the motor.
*
2
Parameter L3-04 should be disabled when a Braking Resistor or Braking Resistor Unit is connected.
*
3
Overload protection may be triggered at lower levels if output frequency is below 6 Hz.
*
4
Protection may not be provided under the following conditions as the motor windings are grounded internally during run:
• Low resistance to ground from the motor cable or terminal block.
• Drive already has a short-circuit when the power is turned on.