Motor 2 Setup: E4
* 1. The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200 V class Inverter of 0.4 kW is given.
* 2. The factory setting depends upon the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given.
* 3. The setting range will depend upon the Inverter capacity. The value for a 200 V class Inverter of 0.4 kW is given.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
E4-01
Motor 2
rated current
Sets the motor rated current.
This set value will become a
reference value for motor pro-
tection and torque limits.
This parameter is an input data
for autotuning.
0.32
to 6.40
*1
1.90 A
*2
No A A A A 321H
6-48
6-117
Motor Rated
FLA
E4-02
Motor 2
rated slip
Sets the motor rated slip.
This set value will become a
reference value for slip com-
pensation.
This parameter is automati-
cally set during autotuning.
0.00 to
20.00
2.90 Hz
*2
No A A A A 322H 6-117
Motor Rated
Slip
E4-03
Motor 2 no-
load current
Sets the motor no-load cur-
rent.
This parameter is automati-
cally set during autotuning.
0.00 to
1.89
*3
1.20 A
*2
No A A A A 323H 6-117
No-Load
Current
E4-04
Motor 2
number of
poles (num-
ber of poles)
Sets the number of motor
poles.
This value is an input data for
autotuning.
2 to 48 4 poles No No A No A 324H 6-117
Number of
Poles
E4-05
Motor 2
line-to-line
resistance
Sets the motor phase-to-phase
resistance in units.
This parameter is automati-
cally set during autotuning.
0.000
to
65.000
9.842
*2
No A A A A 325H 6-117
Mid
Frequency
E4-06
Motor 2 leak
inductance
Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This parameter is automati-
cally set during autotuning.
0.0 to
40.0
18.2%
*2
No No No A A 326H 6-117
Leak Induc-
tance
E4-07
Motor 2
rated capac-
ity
Sets the rated output of the
motor in units of 0.01 kW.
This parameter is an input data
for autotuning.
0.40 to
650.00
0.40
*2
No A A A A 327H 6-117
Mtr Rated
Power