2.2 Basic Module
2.2.5 Built-in SVB Module
2-38
Transmission Distance and Maximum No. of Slave Stations
* The values in parentheses apply when a JEPMC-REP2000 Repeater is used.
JEPMC-REP2000 Repeater must be used if 17 or more slave stations are connected when using MECHATROLINK-II
communication.
( 3 ) Module Configuration
[ a ] Module Configuration Window
Click MP2300S in the Controller area to display the details of the basic module functions in the Module Details area.
The cell No.3 provides a detailed definition of the built-in SVB module.
Communication Method Transmission Distance (Total Network Length)
Maximum Number of Slave
Stations
MECHATROLINK-I
50 m
(can be extended to 100 m by connecting repeaters)
14
MECHATROLINK-II
30 m
(can be extended to 100 m by connecting repeaters)
16 (21)
*
50 m
(can be extended to 100 m by connecting repeaters)
15 (21)
*