3 Electrical Installation
YASKAWA Europe TOEP C710616 88A - AC Drive A1000 IP23/54 Floor Standing - Quick Start Guide EN 15
Wiring Specification
Main Circuit
Power Cable, Ground Wire and Motor Shield Connection
Connect power supply and motor cables as shown below. Use a saddle clamp for fixing the motor cable to make sure the
cable shield is properly connected to ground. The power supply ground wire shall be connected to the earth bar at the
bottom of the panel. The motor cable ground wire shall be connected to the drive or alternatively to the earth bar at the
panel bottom.
Use motor cables and ground connections as recommended below.
Sizes and tightening torque values for L1/L2/L3 and T1/T2/T3 terminals vary depending on the panel configuration.
Model A14
0208 0250 0296 0362 0414 0515 0675
Recommended Motor Cable (mm²) 95 120 185 240 2× 95 2× 120 4× 95
Ground Wire Connection to Earth Bar at Panel Bottom
Stud Size M8 M10
Torque (Nm) 10 20
Ground Wire Connection to Drive Terminals
Stud Size M10 M12 2 x M8
Torque (Nm) 20 32 10
Fix motor cable shield
using a saddle clamp
Power supply ground wire
connection
Motor cable ground wire
connection
Example configuration:
Power supply connection
L1/L2/L3
Motor cable connection
U/T1, V/T2, W/T3
Output motor cable
fixing points
Connect the power supply
ground wire here
The motor cable ground wire can
be connected here or directly to
the drive