6. PROGRAMMING FEATURES
Factory settings of the constants are shown as in the tables.
Constant Set-up and Initialization
The following table describes the data which can be set or read when n001
is set.
Unused constants among n001 to n179 are not displayed.
“”
appears on the LED display for one second and the set data returns to its
initial values in the following cases :
(1) The set values of multi-function input selection 1 to 7 (n050 to n056) are the same.
(2) If the following conditions are not satisfied in the V/f pattern setting :
Max. output frequency (n011) Max. voltage output frequency (n013)
> Mid. output frequency (n014)
Min. output frequency (n016)
For details, refer to Adjusting torque according to application (V/f pattern setting) on page 42.
(3) If the following conditions are not satisfied in the Jump frequency setting :
Jump frequency 3 (n085) Jump frequency 2 (n084)
Jump frequency 1 (n083)
(4) If Frequency reference lower limit (n034) Frequency reference upper limit (n033)
(5) If motor rated current (n036) 150% of inverter rated current
(6) Constant n018 is set to 1 (accel / decel time unit is 0.01sec.) when n018 is set to 0 and the
value exceeding 600.0sec. is set to accel / decel time (n019 to n022).
41
Refer to page 73.
* Excluding setting disabled constants.
n001 Setting
0 n001
Constant that can be set Constant that can be referred
1
2
3
4
5
6
7 to 11
12
13
n001 to n049 *
n001 to n079 *
n001 to n119 *
n001 to n179 *
Not used
Fault history cleared
Not used
Initialize
Initialize (3-wire sequence)
n001 to n179
n001 to n049
n001 to n079
n001 to n119
n001 to n179
Constant selection/initialization (n001)
NOTE