YASKAWA VS MINI J7 Manuel d'utilisateur Page 116

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 123
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 115
116
64 0140H
Motor rated slip
0.0 to 20.0Hz
(Note 2)
0.1Hz
No.
Name
Setting
Range
Register
No. for
Trans-
mission
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page
59 013BH
Overtorque detection
function
0 to 4
0
1
60 013CH
Overtorque detection level
30 to 200%
160%
1%
61 013DH
Overtorque detection time
0.1 to 10.0s
0.1s
0.1s
62 013EH
Hold output
0, 1
0
1
63 013FH
Torque compensation gain
0.0 to 2.5
1.0
0.1
51
51
51
64
39
66 0142H
Slip compensation gain
0.0 to 2.5
0.0
0.1
67 0143H
Slip compensation
time constant
0.0 to 25.5s
2.0s
0.1s
65 0141H
Motor no-load current
0 to 99%
(Note 2)
1%
71
71
68 0144H
MEMOBUS timeover
selection
0 to 4
0
1
69 0145H
MEMOBUS frequency
reference and frequency
monitor unit
0 to 3
0
1
70 0146H
MEMOBUS slave address
0 to 32
0
1
71 0147H
MEMOBUS BPS selection
0 to 3
2
1
72 0148H
MEMOBUS parity selection
0 to 2
0
1
73 0149H
Transmission waiting time
10 to 65ms
10ms
1ms
74 014AH
RTS control
0, 1
0
1
78 014EH
Fault history
Stores, displays
most recent
alarm
Setting disabled
79
Notes:
3. Changes depending on inverter capacity. Refer to page 58.
4. Initial setting of the model with digital operator (without potentiometer) is 1.
Setting can be set to 0 by constant initialization.
1. Upper limit of setting range and initial setting are doubled at 400 class.
2. Changes depending on inverter capacity Refer to the next page.
014FH
Software version No.
Displays lower-
place 3 digits of
software No.
75
#1
014BH
Reducing carrier
frequency
selection at low speed
0, 1
0
1
58
76
#1
014CH
Constant copy function
selection
rdy, rEd, Cpy,
vFy, vA, Sno
rdy
75
77
#1
014DH
Constant read selection
prohibit
0, 1
0
1
76
34
Setting disabled
Vue de la page 115

Commentaires sur ces manuels

Pas de commentaire