70
• Stall prevention (current limit) level during running (n57)
Sets the stall prevention (current limit) level during running in units of 1%
(Inverter rated current = 100%).
* Factory setting: 160%
A setting of 200% disables the stall prevention (current limit) during
running.
If stall prevention action current at agreed speed exceeds the value set for
n57 for longer than 100msec, deceleration starts.
When the output current exceeds the value set for n57, deceleration
continues. When the output current goes down to the value set for n57,
acceleration starts, up to the set frequency.
Stall prevention accel/decel settings during operation are: currently selected
acceleration time 1 (n16), deceleration time 1 (n17) and acceleration time 2
(n18) and deceleration time 2 (n19).
* reduces frequency prevent speed loss
† at acceleration start, output current hysterisis
is approx., 5% of inverter rated current.
• Stall prevention (current limit) function during deceleration (n55)
To prevent overvoltage during deceleration, the inverter automatically
lengthen the deceleration time according to the value of main circuit DC
voltage.