YASKAWA Inverter Manuel d'utilisateur Page 160

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 255
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 159
Maintenance 7 - 3
Preventive Maintenance
If the Drive is used under the following conditions, it may be necessary to inspect more often:
High ambient temperatures, humidity or altitudes above 3,300 feet.
Frequent starting and stopping.
Fluctuations of the AC power supply or load.
Excessive vibration and/or shock loading.
Poor environment, including dust, metal dust, salt, sulfuric acid, chlorine.
Poor storage conditions.
Table 7.3 Preventive Maintenance
Inspection Points Item Check Points Every 3-6 Months Yearly
General
Environment
Ambient temperature
Humidity
Dust
Harmful gas
Oil mist
X
X
X
X
X
Equipment Abnormal vibration or noise X
AC Power Supply Main circuit & control voltage X
AC Power Circuit &
Devices
Conductors & Wire
Connections
Loose lugs, screws & wires
Hot spots on parts
Corrosion
Bent conductors
Breakage, cracking or discoloration
Check spacing
X
X
X
X
X
X
Transformers & Reactors Discoloration or noise X
Terminal Blocks Loose, damaged X
DC Bus Capacitors
Leakage
Ruptures, broken, expansion
Capacitance & insulation
resistance
X
X
X
Relays & Contactors
Noisy
Contact discoloration
X
X
Soft Charge Resistors
Cracked
Discoloration
X
X
Control Circuits Operation
Speed reference voltage/current
I/O contact operation
X
X
Cooling System Cooling Fans/Fins & Heatsink
Abnormal fan noise
Loose connectors
Free of accumulation
X
X
X
Keypad/Display Digital Operator
LEDs
Monitor display values
Key functionality
Clean
X
X
X
X
Vue de la page 159
1 2 ... 155 156 157 158 159 160 161 162 163 164 165 ... 254 255

Commentaires sur ces manuels