Setting 80: HAND Mode
Closing this input will put the drive in HAND Mode.
If this contact is closed within one second of power-up, the drive will honor the utility delay time.
Note: When inputs 80 and 81 are closed simultaneously, input 80 has priority and P5-01 determines the frequency reference.
Setting 81: HAND Mode 2
Closing this input will put the drive in HAND Mode using P5-05 as a frequency reference.
If this contact is closed within one second of power-up, the drive will honor the utility delay time.
Note: When inputs 80 and 81 are closed simultaneously, input 80 has priority and P5-01 determines the frequency reference.
Settings 83, 84, and 85: Alternate Multi-step Setpoints
These setpoint selections are different from Multi Setpoints 1 and 2 (H1-oo = 8D/8E) in that each input is dedicated to a
setpoint instead of being a binary selection.
Table 4.22 shows active setpoints based on the Alternate Multi-Setpoint Selections (H1-oo = 83 to 85):
Table 4.22 Active Setpoints by H1-oo Setting
Alternate Multi-Setpoint Q1-02
H1-oo = 83
Alternate Multi-Setpoint Q1-03
H1-oo = 84
Alternate Multi-Setpoint Q1-04
H1-oo = 85
Setpoint
Open Open Open Q1-01
Closed Open/Closed Open/Closed Q1-02
Open Closed Open/Closed Q1-03
Open Open Closed Q1-04
Setting 88: Volute-Thermostat (N.O.)
Closed: Drive will trip on “VLTS - Volute-TStat Flt”.
Open: Thermostat fault not active.
Note: Assigning both 88 and 89 to input terminals will trigger a VLTS-Volute-TStat Flt.
Setting 89: Volute-Thermostat (N.C.)
Closed: Thermostat fault not active.
Open: Drive will trip on “VLTS - Volute-TStat Flt”.
Note: Assigning both 88 and 89 to input terminals will trigger a VLTS-Volute-TStat Flt.
Setting 8C: Disable Pre-Charge
Close to disable pre-charge.
Settings 8D and 8E: Multi Setpoints 1 and 2
Settings 8D and 8E will override all other PID setpoints when closed.
Table 4.23 Multi Setpoints 1 and 2
Multi Setpoint 1
(H1-0o = 8D)
Multi Setpoint 2
(H1-0o = 8E)
Setpoint Source
Open Open
Frequency Ref (dependent on b1-01), Setpoint 1 - Q1-01 (when b1-01 = 0),
Analog Setpoint (H3-0o = C), Pulse Input Setpoint (H6-01 = 2), or
MEMOBUS setpoint.
Closed Open Setpoint 2 – Q1-02
Open Closed Setpoint 3 – Q1-03
Closed Closed Setpoint 4 – Q1-04
Setting 8F: Low Water Level
Function is active in AUTO Mode during normal operation and is also used with Pre-charge function.
Function depends on P1-30, Low Water Digital Input Configuration, setting.
When P1-30 = 0 (N.O.): Closed: Low Water Level Fault. Open: Reservoir/Tank is filled to normal level.
When P1-30 = 1 (N.C.): Closed: Reservoir/Tank is filled to normal level. Open: Low Water Level Fault.
Pre-charge function uses low water level input as “Tank/Reservoir” feedback to indicate water level reached.
4.8 Detailed iQpump Parameter Descriptions
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
139
4
Start-Up Programming
& Operation