6. Programming Features
147
Unit Selection for Frequency Reference Setting/
Display
Constants and Monitor Displays for Which Selection of Unit
Function is Valid
Setting/Displaying Unit Selection for Frequency Reference
(n035)
The frequency reference, output frequency, and the numeric data of fre-
quency reference constants can be displayed in %, min
-1
, or m/min
according to the set value of constant n035.
Item Contents
Frequency refer-
ence constants
Frequency References 1 to 8 (Constants n024 to n031)
Jog Frequency Reference (Constant n032)
Frequency References 9 to 16 (Constants n120 to n127)
Monitor display Frequency Reference Display (FREF)
Output Frequency Display (FOUT)
Frequency Reference Display (U-01)
Output Frequency Display (U-02)
Constant
No.
Constant Name Description Factory
Setting
n035 Setting/Display-
ing Unit Selec-
tion for
Frequency Ref-
erence
0: Units of 0.01 Hz (less than
100 Hz) 0.1 Hz (100 Hz and
more)
1: Units of 0.1 %
2 to 39: Units of min
-1
(set the
number of motor poles)
40 to 3999: Any unit
0