A.4 Drive Specifications
Note: For optimum performance life of the drive, install the drive in an environment that meets the environmental conditions.
Item Specification
Control
Characteristics
Control Method V/f Control
Frequency Control Range 0.01 to 400 Hz
Frequency Accuracy
Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)
Analog input: within ±0.5% of the max output frequency (25 °C ±10 °C)
Frequency Setting Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/1000 of maximum output frequency
Output Frequency Calculation Resolution
1/2
20
x Maximum output frequency (E1–04)
Frequency Setting Signal
Main frequency reference: 0 to +10 Vdc (20 kΩ),
4 to 20 mA (250 Ω), 0 to 20 mA
(250 Ω)
Starting Torque 150%/3 Hz
Speed Control Range 1: 20~40
Accel/Decel Time 0.00 to 6000.0 s (allows four separate settings for accel and decel)
Braking Torque
Instantaneous Average Decel Torque
<1>
: 0.1/0.2 kW: over 150%, 0.4/0.75 kW:
over 100%, 1.5 kW: over 50%, 2.2 kW and above: over 20%
Continuous Regen Torque: 20%,
125% with a Braking Resistor Unit
<2>
: (10% ED) 10 s with an internal braking
resistor.
V/f Characteristics User-set, programmable.
Functions
Momentary Power Loss Ride-Thru
Speed Search
Multi-Step Speed (9 steps max)
Accel/Decel Time Switch
S-Curve Accel/Decel
3-Wire Sequence
Cooling Fan ON/OFF
Slip Compensation
Torque Compensation
Jump Frequencies (reference dead band)
Frequency Reference Upper/Lower Limit
DC Injection Braking (start and stop)
Overexcitation Braking
Fault Reset
Protection Functions
Motor Protection Motor overheat protection via output current sensor
Overcurrent Protection Drives stops when output exceeds 200% of the rated current (Heavy Duty)
Overload Protection
A stop command will be entered after operating at 150% for 60 s (Heavy Duty)
<3>
Low Voltage Protection
Drive stops when DC bus voltage falls below the levels indicated:
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V), 350
V (3-phase 380 V)
Momentary Power Loss Ride-Thru Stops after 15 ms
Heatsink Overheat Protection Protected by thermistor
Braking Resistor Overheat Protection Overheat input signal for braking resistor (Optional ERF-type, 3% ED)
Stall Prevention
During acceleration and during run: Separate settings for each type of stall
prevention determine the current level at which stall prevention is triggered.
During deceleration: Select, enable/disable.
Cooling Fan Failure Protection Circuit protection (“fan-lock” sensor)
Ground Protection
Electronic circuit protection
<4>
DC Bus Charge LED Remains lit until DC bus voltage falls below 50 V
A.4 Drive Specifications
YASKAWA ELECTRIC SIEP C710606 31A YASKAWA AC Drive – J1000 Technical Manual
173