9 Troubleshooting
9-24
(2) Linear Servomotors
Problem Probable Cause Investigative Actions Corrective Actions
Linear
Servomotor Does
Not Start When
Using JOG
Operation or Host
Controller
Reference.
The control power supply is not
ON.
Check voltage between control
power supply terminals.
Correct the control power circuit.
The main circuit power supply is
not ON.
Check the voltage between power
supply terminals.
Correct the power circuit.
Wrong wiring or disconnection of I/
O signal connector CN1
Check if the connector CN1 is prop-
erly inserted and connected.
Correct the connector CN1 connec-
tion.
Linear servomotor cable or linear
connection cables disconnected.
Check the wiring. Correct the wiring.
The linear servomotor is over-
loaded.
Run under no load and check the
load status.
Reduce load or replace with larger
capacity linear servomotor.
Settings for input signals PnB03 to
PnB12 are incorrect.
Check settings of input signals
PnB03 to PnB12.
Correct the settings of input signals
PnB03 to PnB12.
A servo ON command was not
input.
Check the command sent from the
host controller.
Send a servo ON command.
The forward run prohibited (P-OT)
and reverse run prohibited (N-OT)
input signals are turned OFF.
Check P-OT or N-OT input signal.
Turn P-OT or N-OT input signal
ON.
The current position of the servo-
motor is outside the software limit
setting range.
Check the error at the INDEXER
Module.
Check the motor position and soft-
ware limit setting (PnB21, PnB23),
then move the servomotor into the
software limit setting range.
There is not position reference, or it
is incorrect.
Check the error at the INDEXER
Module.
Set the program table correctly.
The polarity detection is not exe-
cuted.
Check the parameter Pn080. Correct the setting of Pn080.
Check the command sent from the
host controller.
When using an incremental linear
scale, send the servo ON command.
When using an absolute linear
scale, execute polarity detection
(Fn080).
The safety input signal (/HWBB1 or
/HWBB2) remains OFF.
Check the /HWBB1 or /HWBB2
input signal.
Set the /HWBB1 or /HWBB2 input
signal to ON.
When not using the safety function,
mount the safety function jumper
connector (provided as an acces-
sory) on the CN8.
A SERVOPACK fault occurred. Replace the SERVOPACK.
Linear
Servomotor
Moves
Instantaneously,
and then Stops
Linear servomotor wiring is incor-
rect.
Check the linear servomotor wiring.
Correct the linear servomotor wir-
ing.
Serial converter unit wiring is incor-
rect.
Check the serial converter unit wir-
ing.
Correct the serial converter unit
wiring.
Linear scale wiring is incorrect. Check the linear scale wiring. Correct the linear scale wiring.
Linear scale pitch (Pn282) is incor-
rect.
Check the setting of Pn282. Correct the setting of Pn282.
Linear scale counting up direction
and motor moving coil forward
direction do not agree.
Check the directions.
Change the setting of Pn080.1
(Motor Phase Selection).
Match the linear scale direction and
moving coil direction.
Polarity detection is not performed
correctly.
Check if the value of Un004 (Elec-
tric Angle 2, angle from polarity
origin) at an arbitrary position is
between ±10 degrees.
Correct the settings for the polarity
detection related parameter.
Linear
Servomotor
Speed Unstable
Wiring connection to linear servo-
motor is defective.
Check connection of power lead
(phases U, V, and W) and the con-
nectors of serial converter unit con-
nection cables.
Tighten any loose terminals or con-
nectors.