4.8 Detailed iQpump Parameter Descriptions
This section explains the basic settings required for initial drive operation. Checking these basic parameter settings will help
to ensure a successful drive start-up. Refer to Parameter List on page 227 for a complete listing of drive parameters if more
information is required for parameters not listed in this section.
Parameter Name Page
A1-01 Access Level Selection 119
A1-03 Initialize Parameters 120
b1-01 Frequency Reference Selection 1 121
b1-02 Run Command Selection 1 124
b1-03 Stopping Method Selection 125
b3-01 Speed Search Selection at Start 127
b5-01 PID Function Setting 127
b5-03 Integral Time Setting (I) 128
b5-09 PID Output Level Selection 128
b5-39 PID Setpoint Display Digits 128
C1-01 to
C1-04
Accel, Decel Times 1 and 2 128
E2-01 Motor Rated Current 129
E2-04 Number of Motor Poles 129
H1-01 to
H1-07
Functions for Terminals S1 to S7 129
H2-01 to
H2-03
Terminal MA/MB/MC, P1/PC, and P2/PC
Function Selection
140
H3-01 Terminal A1 Signal Level Selection 149
H3-02 Terminal A1 Function Selection 149
H3-03,
H3-04
Terminal A1 Gain and Bias Settings 149
H3-09 Terminal A2 Signal Level Selection 150
H3-10 Terminal A2 Function Selection 150
H3-11,
H3-12
Terminal A2 Gain and Bias Setting 150
H4-01
Multi-Function Analog Terminal AM Monitor
Selection
151
H4-02,
H4-03
Multi-Function Analog Output Terminal AM
Gain/Bias
151
L5-01 Number of Auto Restart Attempts 151
L5-04 Fault Reset Interval Time 152
o1-08 Third Line User Monitor Selection 152
P1-01 Pump Mode 152
Parameter Name Page
P1-02 System Units 152
P1-03 Feedback Device Scaling 153
P1-04 Start / Draw Down Level 153
P1-05 Start Level Delay Time 153
P1-06 Minimum Pump Speed 153
P1-08 Low Feedback Level 153
P1-09 Low Feedback Level Fault Delay Time 153
P1-10 Low Feedback Selection 154
P1-11 High Feedback Level 154
P1-12 High Feedback Level Fault Delay Time 154
P1-13 High Feedback Selection 154
P2-01 Sleep Level Type 155
P2-02 Sleep Level 155
P2-03 Sleep Delay Time 155
P4-01 Pre-Charge Level 155
P4-02 Pre-Charge Frequency 155
P4-03 Pre-Charge Time 156
P4-05 Pre-Charge Loss of Prime Level 159
P4-06 Pre-Charge Frequency 2 159
P4-07 Pre-Charge Time 2 159
P4-08 Pre-Charge Loss of Prime Level 2 159
P4-10
AUTO Mode Operator Run Power Down
Storage
159
P4-11 Thrust Bearing Acceleration Time 159
P4-12 Thrust Bearing Frequency 159
P4-13 Thrust Bearing Deceleration Time 160
P4-17 Utility Start Delay 160
P4-32 Pre-Charge Level 2 160
P5-02 HAND Reference 1 161
P5-04 HAND Key Function Selection 161
Q1-01 PID Controller Setpoint 1 161
n
A1-01: Access Level Selection
Allows or restricts access to drive parameters.
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 3 2
Setting 0: Operation only
Access to only parameters A1-01, A1-04, and all U monitor parameters.
Setting 1: User Parameters
Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
All parameters can be viewed and edited.
4.8 Detailed iQpump Parameter Descriptions
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
119
4
Start-Up Programming
& Operation
Commentaires sur ces manuels