Network Communications 3-11
# Fast I/O Input Data
This area is used to transfer parameter data directly from the drive dual port RAM interface. The following tables detail the functions of the
fast I/O input data (Bytes 0 to 5)
Table 3.14 – 3 Word input/Output Message Fast I/O Input Data
Fast I/O Input Data (Drive -> PROFIBUS-DP Master )
Byte Function Bit Note
0h @ RUN
1h @ Zero Speed
2h @ Reverse
3h @ Reset Signal
4h @ Frequency Agree
5h @ Drive Ready (Rdy)
6h @ Minor Fault (Alarm)
0
7h @ Major Fault
8h @ OPE Error
9h @ Fault Restart
Ah Local/Remote 1 = Remote Operation
Bh Multi-Function Output 1 1 = Close
Ch Multi-Function Output 2 1 = Close
Dh Multi-Function Output 3 1 = Close
Eh Motor Select 1 = #2 Motor
1
Drive
Status
Fh @ Zero Servo Complete
2 Frequency Reference MSB
3
Frequency
Reference
Frequency Reference LSB
0.1Hz
scaling is dependent on the setting of parameter o1-03
4 Output Current MSB
5
Output Current
Output Current LSB
Calculated value
Drive Current(Drive Rating/8192)