4.7 iQpump Presets and Functions
Table 4.8 iQpump Presets and Functions
Feature Name Preset or Function Page
Pump Down Level Control Preset 105
General Purpose Mode Preset 107
Low City or Low Suction Inlet Pressure Function 108
Current Limit Function 109
Speed Follower Deceleration Time Switchover Function 110
Software (MEMOBUS) Multiplexing Setup Function 111
Simple Duplex System Application Function 115
Multiplexing Stop History Function 118
u
iQpump Presets
n
Pump Down Level Control Application Preset
This preset allows the drive to regulate the depth of water in a tank or other vessel that is being filled by an external source.
A feedback device that measures water depth is wired to the drive. A PI-control process loop will then modulate the pump
speed to pump water out the tank to keep the water depth the setpoint level (pump out at the recharge rate). The drive controller
has an application preset to simplify the start up and control of this application.
System units are in feet (P1-02 = 6).
Feedback device scaling (P1-03). The feedback device scaling must be entered into the drive for proper control.
Minimum pump speed (P1-06). Most pumps cannot be run below a certain speed or cavitation can occur.
Number of Motor Poles (E2-04). The default is for a 2-pole motor.
Sleep Function. The drive controller will sleep when the system demand is low and awaken when demand returns.
Required Control Wiring
Most depth level transducers have current-based feedback (4-20 mA). The A2 terminal of the drive is preset for 4-20 mA and
pre-programmed for PID feedback (H3-10 = B).
Start Up Procedure
1.
Set parameter A1-03 to 6009 (Pump Down Level) to pre-set parameter values for this application.
2.
Set the motor-rated current in parameter E2-01. This information can be found on the motor nameplate or specification
sheet.
3.
Set the number of motor poles in parameter E2-04 (2-pole motors have a rated RPM of slightly less than 3600 RPM;
4-pole motors have a rated RPM of slightly less than 1800 RPM). This information can be found on the motor
nameplate or specification sheet.
4.
Set the feedback device scaling in parameter P1-03. Check the sensor nameplate or specification sheet. For example,
if the device outputs 20 mA at 14.50 ft of water depth, the set P1-03 to 14.50. The drive controller will automatically
scale all associated parameters and monitors. Monitor U1-91 (Pump Feedback) will display the measured water depth
in feet. The drive has a High Feedback Fault set in parameter P1-11. Make sure that P1-11 is appropriately set for
sensor scaling in P1-03.
5.
Set the desired water depth level in parameter Q1-01 (PID setpoint). This is desired water depth that the drive will
regulate the pump speed around. To quickly access this parameter, press the HOME key and then the ENTER key.
The U1-99 monitor on the home screen displays the Q1-01 PID setpoint.
6.
Set the minimum speed that the pump can be run in parameter P1-06. The default is 40 Hz. This information can be
found on the pump specification sheet.
7.
The default setting does not allow the drive to automatically restart after power loss if the drive was running at the
time of power loss. Set P4-10, AUTO Mode Operator Run Power Down Storage, to 1 to enable this feature.
8.
Press the AUTO key to start the drive with PID control (water depth control). Press the OFF key to stop the drive.
9.
The pump can be run in HAND (LOCAL) mode for maintenance purposes by pressing the HAND key while the drive
is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Press AUTO to return the
drive to PID control. The HAND speed reference can be set in P5-02 (Hand Reference 1). Disable the HAND key by
setting P5-04 to 0 (disabled).
10.
Configure the sleep function. The pump can be programmed to shut off or “sleep” if the water falls below the depth
set in parameter P2-02 (Sleep Level). The controller will monitor the water depth feedback signal and wake up when
the water depth rises above the setting in parameter P1-04 (Start/Draw Down Level). Logically, set the Sleep Level
4.7 iQpump Presets and Functions
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
105
4
Start-Up Programming
& Operation