Digital Operator Display Fault Name
oH
Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02.
Cause Possible Solution
Surrounding temperature is too high
Check the temperature surrounding the drive. Verify temperature is within drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Load is too heavy
Measure the output current.
Decrease the load.
Lower the carrier frequency (C6-02).
Internal cooling fan is stopped
Replace the cooling fan. .
After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.
Digital Operator Display Fault Name
oH1
Overheat 1 (Heatsink Overheat)
The heatsink temperature exceeded the drive overheat level.
Cause Possible Solution
Surrounding temperature is too high
Check the temperature surrounding the drive.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.
Load is too heavy
Measure the output current.
Lower the carrier frequency (C6-02).
Reduce the load.
The internal cooling fan has reached its
performance life or has malfunctioned.
Check the maintenance time for the cooling fan (U4-04).
If U4-04 exceeds 90%, replace the cooling fan.
After replacing fan, reset the fan maintenance time (o4-03 = “0”).
Current flowing to control circuit terminal
+V exceeded the tolerance level.
Check the current level of the terminal.
Set the current to the control circuit terminal to be 20 mA or less.
Digital Operator Display Fault Name
oH4
Motor Overheat Fault (PTC Input)
The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level.
Detection requires setting multi-function analog inputs H3-02 or H3-10 to E.
Cause Possible Solution
Motor has overheated
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-04).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
Check the motor rated current.
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.
Digital Operator Display Fault Name
oL1
Motor Overload
The electronic motor overload protection tripped
Cause Possible Solution
Load is too heavy Reduce the load.
Cycle times are too short during
acceleration and deceleration
Increase the acceleration and deceleration times (C1-01 through C1-04).
5.2 Fault Detection