Vue de la page 181
HOA Keypad Display Minor Fault Name
When the drive is powered up for the first
time, the time and date must be set. The
HOA keypad will display the time and date
setup screen for 30 seconds. If a button is
not pressed during this time, the display
will clear and a “Clock Not Set” alarm will
flash.
Pressing the F2 (Data) key will display the setting screen again.
Digital Operator Display Minor Fault Name
CrST Cannot Reset
Cause Possible Solution
Fault reset was being executed when a run
command was entered.
Ensure that a run command cannot be entered from the external terminals or option card during fault reset.
Turn off the run command.
Digital Operator Display Minor Fault Name
CyC
MECHATROLINK Comm. Cycle Setting Error
Comm. Cycle Setting Error was detected.
Cause Possible Solution
The controller is using a comm. cycle
beyond the allowable setting range for the
MECHATROLINK option unit.
Set the comm. cycle for the upper controller within the allowable setting range for the MECHATROLINK
option unit.
Digital Operator Display Minor Fault Name
dnE Drive Disabled
Cause Possible Solution
“Drive Enable” is set to a multi-function
contact input (H1-oo = 6A) and the
contact is open.
Check the operation sequence.
Digital Operator Display Minor Fault Name
E5 MECHATROLINK Watchdog Timer Error
Cause Possible Solution
The watchdog timer expired while waiting
for data from the controller.
Issue a DISCONNECT or ALM_CLR command, followed by a CONNECT or SYNC_SET command and
move to phase 3.
Digital Operator Display Minor Fault Name
EF
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.
Cause Possible Solution
Sequence error
Check the forward and reverse command sequence and correct the problem.
Note: When minor fault EF detected, motor ramps to stop.
Digital Operator Display Minor Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause Possible Solution
An external fault was received from the
PLC with F6-03 set to 3, which allows the
drive to continue running after an external
fault occurs.
Remove the cause of the external fault.
Remove the external fault input from the PLC.
There is a problem with the PLC program. Check the PLC program and correct problems.
Digital Operator Display Minor Fault Name
EF1
Pump Fault (Input Terminal S1)
External fault at multi-function input terminal S1.
EF2
Pump fault (input terminal S2)
External fault at multi-function input terminal S2.