Yaskawa iQpump Micro Manuel d'utilisateur Page 68

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 300
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 67
Cable gland
(Locknut)
Cable gland
(Body)
Figure 3.12 Inserting the Cable Glands
n
Route Cables Through Cable Glands
Route the cables through the cable glands then tighten the cable gland caps to complete preparation for main circuit and control
circuit wiring.
Cable gland
(Locknut)
Cable gland
(Body)
Cable
Figure 3.13 Cable Routing
u
IP66/NEMA Type 4X Enclosure Front Cover Removal and Installation
NOTICE: Do not attempt to disassemble the protective enclosure surrounding the drive. The protective enclosure is constructed as a single
piece to include the heatsink. Attempting to disassemble the enclosure may void the protective integrity of the enclosure.
1.
Loosen the 4 bolts that attach the enclosure front cover in place, gently move the front cover away from the enclosure.
Refer to Table 3.2 for installation bolt size.
Press firmly on the digital operator cable connector release tab to disconnect the cable from port CN1 on the drive,
then remove the front cover.
Table 3.2 IP66/NEMA Type 4X Enclosure Front Cover Installation Bolt Size and Torque
Voltage Class Drive Model Installation Bolt Size
Tightening Torque Nm (lb-in)
Single-Phase 200 V Class BV0001G to BV0012G M5 2.0 to 2.5 (17.7 to 22.1)
Three-Phase 200 V Class
2V0001G to 2V0020G M5 2.0 to 2.5 (17.7 to 22.1)
2V0030G to 2V0069G M6 5.4 to 6.0 (47.8 to 53)
Three-Phase 400 V Class
4V0001G to 4V0011G M5 2.0 to 2.5 (17.7 to 22.1)
4V0018G to 4V0038G M6 5.4 to 6.0 (47.8 to 53)
3.4 Preparing IP66/NEMA Type 4X Enclosure Drives for Wiring
68
YASKAWA TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Vue de la page 67
1 2 ... 63 64 65 66 67 68 69 70 71 72 73 ... 299 300