100 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Function Code
The function code specifies commands. There are four function codes supported by the drive, as shown below.
Table 36 MEMOBUS / Modbus Function Codes
Data
Configure consecutive data by combining the storage register address (test code for a loopback address) and the data the register contains.
The data length changes depending on the command details.
Error Check
Errors are detected during communication using CRC-16. Perform calculations using the following method:
1. The factory setting for CRC-16 communication is typically zero, but when using the MEMOBUS / Modbus system, set the factory
setting to one (e.g., set all 16 bits to 1).
2. Calculate CRC-16 using MSB as slave address LSB, and LSB as the MSB of the final data.
3. Calculate CRC-16 for response messages from the slaves and compare them to the CRC-16 in the response messages.
Function Code
(Hexadecimal)
Function
Command Message Response Message
Min. (Bytes) Max. (Bytes) Min.* (Bytes) Max. (Bytes)
03H Reading / Holding Register Contents 8 8 7 37
06H Write In Single Holding Register 8 8 8 8
08H Loopback Test 8 8 8 8
10H Write In Several Holding Registers 11 41 8 8
* Minimum bytes for a normal Response Message (error response message is always 5 bytes).