198 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
◆ P4-08 Protection Fault Auto Restart Enable <0032>
Setting Range: 0 ~ 7
Factory Default: 0
Setting to enable / disable Auto Restart for the following iQpump protection faults:
SP: Not Maintaining Setpoint (P1-11)
LOP: Loss of Prime (P1-16)
POC: Pump Over Cycling (P2-08)
Note: Parameter L5-01 needs to be set to “1” and program L5-03 needs to be set to the applicable time.
Figure 1.148
Figure 152. System Fault Auto-Restart Fault Counter
Setting POC LOP SP
0: Disable Disable Disable
1: Disable Disable Enable
2: Disable Enable Disable
3: Disable Enable Enable
4: Enable Disable Disable
5: Enable Disable Enable
6: Enable Enable Disable
7: Enable Enable Enable
System
Auto-
Restart
Counter
Cleared
System Fault Restarts
:
Drive 1
Drive 1
Drive 2
Drive 2
Local Fault Restarts :
Local Fault Restarts :
Auto-Restarting?
Auto-Restarting?
NMS
Fault / Message Display
Fault / Message Display
Fault
NMS EF3 LFB/LW
Net Pump Err
Manual
Fault Reset
Auto
Fault Reset
L5-01 = 5
P4-08 = 7 (
POC=Y LOP=Y SP=Y)
P9-22 = 3
Net Pump Err
EF3
1000212222 3233 1000 111 110
0000100001 0111 0000 000 111
0000000000 0000 0000 000 111
No system fault for 10 min s
NMS HFB/HW
Net Pump Err
EF3
Net Pump ErrNet Pump Err
Auto
Fault Reset
Auto
Fault Reset
Auto
Fault Reset
Auto
Fault Reset
Auto
Fault Reset
No local fault for 10 mins