YASKAWA TM.iQp.07 iQpump Controller Programming Manual 13
Figure 1. 1
Figure 1. 2 and 3-Wire Control Wiring Examples
Important: Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The following parameters will not be reset
when parameter A1-03 = 2220 or 3330:
A1-04 Password Entry
Setting Range: 0 ~ 9999
Factory Default: 0
If parameters A1-01 through A1-03 are locked (unchangeable), they can be unlocked by entering the correct password number into
A1-04.
Once the correct password number is entered and the specified parameters are unlocked, a 2-Wire or 3-Wire initialization will reset the
password to 0000.
Note: A1-04 will return to “0000” when the password has been entered.
A1-05 Select Password
Setting Range: 0 ~ 9999
Factory Default: 0
When the value set into A1-04 does NOT match the value set into A1-05, parameters A1-01 thru A1-03 cannot be changed. All other
parameters determined by A1-01 can be changed. Parameter A1-05 can be accessed by displaying parameter A1-04, then press and hold
the RESET key along with the MENU key simultaneously.
A1-00 Language Selection
E1-03 V/f Pattern Selection
o2-04 kVA Selection
Note: 2-Wire Control is the most commonly used.
Stop switch
(NC contact)
Operation switch
(NO contact)
3-wire control
2-wire control
Run command
(run on momentary close)
Stop command
(stop on momentary close)
Sequence input common
S1
SN
S2
S1
SN
FWD Run/Stop