152 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Table 57 Fault <0034>
P1-13 Hysteresis Level
Setting Range: 0.0 ~ 100.0
Factory Default: 0.0
The iQpump drive can be configured to detect Low Feedback Level (P1-07) and High Feedback Level (P1-09) alarms. The Hysteresis
Level (P1-13) is used to provide a bandwidth before the drive returns to normal operation. The Hysteresis Level is used to prevent rapid
cycling between alarm and normal operations.
The Hysteresis Level (P1-13) works in conjunction with the Low Feedback Level (P1-07) and High Feedback Level (P1-09) functions.
The units for this parameter are determined by the System Units (P1-02).
P1-14 Prime Loss Level
Table 58 Parameters
P1-15 Low / Hi Water Digital Input Congifuration / Water DI Config <0034>
The iQpump drive can be configured to detect a low water level condition. To activate the low water level detection requires one of the
multi-function digital inputs to be programmed for low water level (H1-xx = 85). The multi-function digital input can be configured to
accept a normally closed or normally open contact by programming the Low Water Input (P1-15).
This function is only active during operation in the Auto Mode.
A digital input and fault may be added for “High Water Level” switch. A digital input was created to connect a float or pressure switch to
indicate if the level in the reservoir is too high. This fault will be detected whenever the drive is
Important: Refer to H1-xx = 85 on page 186 for further description of the low water level function.
Function Description: <0034>
The “High Feedback / High Water” will activate based on the PI feedback. However, this fault will also activate based on an digital
input (H1-0x = 88).
The parameter that configures the Normally Open / Normally Closed operation of the Low Water switch has settings which will
configure the added High Water switch.
The High Water condition will be detected anytime the drive is running.
The High Water fault is NOT be auto-restartable.
Fault Display Description Cause Countermeasures
NMS
Setpoint Not Met
Not Maintaining Setpoint
Setpoint cannot be maintained.
When the setpoint can not be maintained for a time specified in
P1-12. Function is disabled when the drive is not running and PID
is not active.
Possible causes: Blocked Impeller, Over-Cycling, Broken Pipe
Difference between setpoint and
feedback is smaller than P1-11
Maximum Setpoint Difference.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description Range Default
Menu
Location
P1-14
0109
Prime Loss Level
Prime Loss Level
Used to detect loss of prime in the pump. If output current drops
below this level for the time specified in P1-12 and the output
frequency is at fmax, a “Loss Of Prime” fault occurs. The drive will
coast to a stop when a fault occurs.
If P1-01 = 3, the function is active on the lead drive, but will stop all
drives running on the network when the system fault occurs.
<0034>
0.0 ~
1000.0
0.0 A Programming
Setting Description
0 Low N.O. - Hi N.O. (Low Water Normally Open / High Water Normally Open)
1 Low N.C. - Hi N.O. (Low Water Normally Closed / High Normally Open)
2 Low N.O. - Hi N.C. (Low Water Normally Open / High Water Normally Closed)
3 Low N.C. - Hi N.C. (Low Water Normally Closed / High Normally Closed)