30 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
b3-05 Speed Search Delay Time
Setting Range: 0.0 ~ 20.0 s
Factory Default: 0.2 s
In cases where an output contactor is used between the iQpump drive and the motor, extra waiting time is provided after power returns
and before Speed Search is performed. This extra time allows for the contactor to operate. When Speed Search at start is used, b3-05 will
serve as the lower limit of the Minimum Baseblock Time (L2-03).
b3-14 Bi-Directional Speed Search Selection
The b3-14 parameter can be used to turn off the bi-directional capabilities of the Speed Estimation form of Speed Search. By turning off
the bi-directional capability, the speed search will only try to match the speed in the last known direction.
Setting Description
0Disabled
1 Enabled (factory default)