Time Delayed External Fault(s)
Allow all external faults to have a settable time delay.
- An “On-Delay” timer will be applied to the external fault if it is “Normally Open”.
- An “Off-Delay” timer will be applied to the external fault if it is “Normally Closed”.
- If the external fault is set to “During Run”, the time delay will start after a run command is received.
Figure 1.59
Figure 59. External Fault 3 - Normally Open, Always Detected, Coast To Stop
Figure 1.60
Figure 60. External Fault 3 - Normally Closed, Always Detected, Coast To Stop
EF3 Input
(H1-01 = 24 )
External Fault 3 – Normally Open, Always Detected , Coast To Stop
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
Fault Reset
Input
Run
Command
Output
Frequency
Fault Output
(External Fault 3)
EF3 Input
(H1-01 = 25 )
External Fault 3 – Normally Closed, Always Detected, Coast To Stop
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
H1-12
EF3 Delay Tm
Fault Reset
Input
Run
Command
Output
Frequency
Fault Output
(External Fault 3)