YASKAWA TM.iQp.07 iQpump Controller Programming Manual 289
P9-04
<0034>
0883
Alternation Mode
Alternation Mode
Determines how alternation is performed:
0: FIFO Auto
1: FIFO Forced
2: LIFO
0 ~ 2 0 Programming
P9-05
<0034>
0884
Lag Drive Mode
Lag Drive Mode
Determines how the lag drives function.
0: Fixed Speed - Runs at the P9-06 setting.
1: PI Regulation - Uses PI to determine speed.
0 ~ 1 0 Programming
P9-06
<0034>
0885
Lag Fixed Speed
Lag Fixed Speed
When the drive changes from a lead to a lag and P9-05 = 0, the drive
will run at this speed after P9-07 delay time expires.
0.0 ~
120.0 Hz
55.0 Hz Programming
P9-07
<0034>
0886
Lag Fixed Speed Delay
Lag Fixed Spd Dly
When the drive changes from a lead to a lag and P9-05 = 0, this time
specifies how long before the drive runs at the P9-06 speed.
0 ~ 1000 s 5 s Programming
P9-08
<0034>
0887
Add Pump Mode
Add Pump Mode
Selects the detection method for staging a new pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
0 ~ 2 0 Programming
P9-09
<0034>
0888
Add Freq Level
Add Freq Lvl
When P9-08 = 0 and the output frequency rises above this level for the
time set in P9-11, the lead drive will request for a new lead drive
through the iQpump Memobus Network.
When P9-08 = 2 and the output frequency rises above this level the
delta feedback (setpoint - feedback) has exceeded the level set in
P9-10 for the time set in P9-11, the lead drive will request for a new
lead drive through the iQpump Memobus network.
0.0 ~
120.0 Hz
56.0 Hz Programming
P9-10
<0034>
0889
Add Delta Level
Add Delta Lvl
When P9-08 = 1 and the delta feedback (setpoint - feedback) has
exceeded this level for the time set in P9-11, the lead drive will request
for a new lead drive through the iQpump Memobus Network.
When P9-08 = 2 and the delta feedback (setpoint - feedback) has
exceeded this level and the output frequency is above P9-09 for the
time set in P9-11, the lead drive will request for a new lead drive
through the iQpump Memobus network.
0 ~ 6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
P9-11
<0034>
088A
Add Delay Time
Add Dly Time
Delay time before a new lead drive is added to the system. 0 ~ 3600 s 10 s Programming
P9-12
<0034>
088B
Remove Pump Mode
Remove Pump Mode
Selects the detection method for de-staging to the previous lead pump:
0: Output Frequency
1: Feedback
2: Feedback + Fout
0 ~ 2 0 Programming
P9-13
<0034>
088C
Remove Freq Level
Remove Freq Lvl
When P9-12 = 0 and the output frequency drops below this level for
the time set in P9-15, the lead drive will request to be removed from
the system through the iQpump Memobus network.
When P9-12 = 2 and the output frequency drops below this level and
the delta feedback (feedback - setpoint) has exceeded the level set in
P9-14 for the time set in P9-15, the lead drive will request to be
removed from the system through the iQpump Memobus network.
0.0 ~
120.0 Hz
40.0 Hz Programming
P9-14
<0034><003
4>
088D
Remove Delta Level
Remove Delta Lvl
When P9-12 = 1 and the delta feedback (feedback - setpoint) has
exceeded this level for the time set in P9-15, the lead drive will request
to be removed from the system through the iQpump Memobus
network.
When P9-12 = 2 and the delta feedback (feedback - setpoint) has
exceeded this level and the output frequency is below P9-13 for the
time set in P9-15, the lead drive will request to be removed from the
system through the iQpump Memobus network.
0 ~ 6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
P9-15
<0034>
088E
Remove Delay Time
Remove Dly Time
Delay time before the lead drive is removed from the system. 0 ~ 3600 s 10 s Programming
P9-16
<0034>
088F
Stabilization Time
Stabilization Time
Time used to stabilize the system when a pump is staged or de-staged.
Lead-lag control and pump protection is suspended during this time.
0 ~ 3600 s 3 s Programming
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.