Yaskawa iQpump Controller Programming Manual Manuel d'utilisateur Page 169

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 302
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 168
YASKAWA TM.iQp.07 iQpump Controller Programming Manual 169
Figure 1.120
Figure 124.
Figure 1.121
Figure 125.
Figure 1.122
Figure 126.
The sleep function can be active during the following conditions:
When P2-20 is set to 0 or 3
<0034> (disabled), the output frequency must be greater than the Sleep Level (P2-02).
When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See
Figure 124..
When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20). See Figure 125..
When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20) and Sleep Level (P2-02). See Figure 126.
A value of 0 programmed in P2-20 will disable this function.
P2-01 = 0: Display based on “Hz”
<0034>
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03
P1-06
SLEEP PERMITTED
P2-02
P2-20
P2-03
SLEEP MODE
P1-06
SLEEP MODE
SLEEP PERMITTED
P2-02
P2-20
P2-03
Vue de la page 168
1 2 ... 164 165 166 167 168 169 170 171 172 173 174 ... 301 302

Commentaires sur ces manuels

Pas de commentaire