The sleep function can be active during the following conditions:
• When P2-20 is set to 0 or 3
<0034> (disabled), the output frequency must be greater than the Sleep Level (P2-02).
• When P2-20 is greater than P2-02, the output frequency must be greater than Alternative Sleep Activation Level (P2-20). See
Figure 124..
• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20). See Figure 125..
• When P2-20 is greater than 0 and less than P2-02, the output frequency must be greater than Alternative Sleep Activation Level
(P2-20) and Sleep Level (P2-02). See Figure 126.
A value of 0 programmed in P2-20 will disable this function.