YASKAWA TM.iQp.07 iQpump Controller Programming Manual 115
Figure 1.93
Figure 97. Motor Overload Protection Time based on Output frequency and Load
◆ L1-03 Motor Overheat Alarm Operation Selection
◆ L1-04 Motor Overheat Fault Operation Selection
◆ L1-05 Motor Temperature Input Filter Time
Setting Range: 0.00 ~ 10.00 s
Factory Default: 0.20 s
The iQpump drive can be programmed to accept a PTC (Positive Temperature Coefficient) Thermistor input for monitoring motor
temperature. By setting parameter H3-09 = “E: Motor Temperature,” and attaching the PTC thermistor per the Figure 98. below, the
iQpump drive can react to the increasing motor winding temperature with both an alarm (L1-03) and a fault (L1-04).
Setting Description
0 Ramp to Stop
1Coast to Stop
2Fast-Stop
3 Alarm Only (factory default)
Setting Description
0 Ramp to Stop
1 Coast to Stop (factory default)
2Fast-Stop
Output Current
(Percent of motor FLA)