YASKAWA TM.iQp.07 iQpump Controller Programming Manual 51
E1 V/f Pattern
◆ E1-01 Input Voltage Setting
Setting Ranges: 155.0 V ~ 255.0 V (208 V / 240 V Models)
310.0 V ~ 510.0 V (480 V Models)
Factory Defaults: 208.0 V (208 V Models)
240.0 V (240 V Models)
480.0 V (480 V Models)
Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the levels of
some protective features of the iQpump drive (i.e. Overvoltage, Stall Prevention, etc.). E1-01 also serves as the Maximum / Base Voltage
used by the Preset V / Hz curves (E1-03 = 0 ~ D).
◆ E1-03 V/f Pattern Selection
The iQpump drive operates utilizing a set V/f pattern to determine the appropriate output voltage level for each commanded speed. There
are 14 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum voltage is
reached), and maximum frequencies.
There are also settings for Custom V/f patterns that will allow the programmer to manually set (“Customize”) the V/f pattern using
parameters E1-04 through E1-13.
Using parameter E1-03, the programmer can select one of the preset V/f patterns or chose between a custom V/f pattern with an upper
voltage limit (E1-03 = “F: Custom V/f”) and a custom V/f pattern without a voltage limit (E1-03 = “FF: Custom w/o limit”).
Setting Description
050 Hz
1 60 Hz Saturation
2 50 Hz Saturation
372 Hz
450 Hz VT1
550 Hz VT2
660 Hz VT1
760 Hz VT2
850 Hz HST1
950 Hz HST2
A60 Hz HST1
B60 Hz HST2
C90 Hz
D120 Hz
E 180 Hz (invalid - OPE2 fault will occur)
F Custom V/f (factory default
, with parameter values per setting 1)
FF Custom w/o limit