YASKAWA TM.iQp.07 iQpump Controller Programming Manual 163
The Sleep Mode: Cycling Protection (P2-06) works in conjunction with the Sleep Mode: Maximum Cycling Protection Time (P2-07).
If P1-01 = 3, the function is active when there is only one drive running on the network.
<0034>
P2-07 Sleep Mode: Maximum Cycling Protection Time
Setting Range: 0 ~ 3600 s
Factory Default: 300 s
The iQpump drive can be configured to allow a maximum number of cycles before initiating a “Pump Over Cycle Fault (POC).” The
number of cycles allowed is determined by programming the Sleep Mode: Cycling Protection (P2-06). The maximum time allowed
between cycles can be programmed in the Sleep Mode: Maximum Cycling Protection Time (P2-07). If no cycling occurs within the
programmed time, the drive will reset the internal cycle register.
The Sleep Mode: Maximum Cycling Protection Time (P2-07) works in conjunction with the Sleep Mode: Cycling Protection (P2-06).
P2-08 Over-Cycling Mode
If P2-08 = “0: Disabled,” the over-cycling mode is disabled.
If P2-08 = “1: Alarm,” then a “Pump Cycling” alarm will occur to indicate a pump over-cycle condition when the maximum number of
cycles has been reached as defined by the Sleep Mode: Cycling Protection (P2-06).
If P2-08 = “2: Pump Over Cycle Fault (POC),” then a “Pump Over Cycle (POC)” fault will occur to indicate a pump over-cycle fault
condition, when the maximum number of cycles has been reached, as defined by the Sleep Mode: Cycling Protection (P2-06).
If P2-08 = “3: Auto Compensation,” then the drive will automatically increase (compensate) the system setpoint by the value
programmed in the setpoint Compensation (P2-09) parameter.
The compensation will increase each time the maximum number of cycles is reached as defined by the Sleep Mode: Cycling Protection
(P2-06) function. When the setpoint is increased (incremented), the internal over-cycle counter will be reset.
The original setpoint will be restored (decreased) in steps defined by Setpoint Compensation (P2-09) when the pump system has been
operating without cycling for the time programmed in the Maximum Cycle Protection Time (P2-07) parameter.
Over-cycle protection is only active during operation in the Auto Mode and in combination with no-flow sleep functions P2-05 and P2-
07.
Note: Maximum setpoint compensation can be programmed in Maximum Setpoint Compensation (P2-10).
Manually starting and stopping the drive will reset the internal over-cycle counter. Transitioning from Hand to Auto Mode will also reset
the internal over-cycle counter.
Setting Description
0Disabled (factory default)
1Alarm
2 Pump Over Cycle Fault (POC)
3 Auto Compensation