72 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
To reset the Low Water Level Fault would require the removal of the run command, initiate a fault reset, and restart the drive using the
Pre-charge function.
IMPORTANT:
<0034>
Program P1-15 to 0 or 2 when the “Low Water” function is not used.
Note: Low Water Level Fault is only active in the Auto Mode and inactive during the Pre-charge function.
Figure 1.55
Figure 55. Lower Water Fault on Operator
Figure 1.56
Figure 56. Wiring Diagram
■ Function: Fixed Speed Auto (Setting: 86)
A digital input can be configured to enable the Fixed Speed Auto (H1-0x = 86) when operating in the Auto Mode. A contact closure into
the multi-function input will enable the Fixed Speed Auto function.
The Fixed Speed Auto will cause the drive to run at the iQpump drive Multi / Maximum Level (P3-02) and disable the PI Control, Sleep
Mode and Lead / Lag operation.
When the digital input is open, the Fixed Speed Auto is disabled.
Note: Pre-charge and Thrust Bearing functions have a higher priority than Fixed Speed Auto.
-DRIVE-
Low FB / Water
LFB /
U2-04 =
U2-05 =
0.00 Hz
0.00 A
External Switch or
Relay Contact
Low Water Level
H1-04 = 85
(Low Water Level)
S1
S2
S3 (H1-01)
S4 (H1-02)
S5 (H1-03)
S6 (H1-04)
S7 (H1-05)
SC
SP 24 VDC +/- 20%, 8 mA
E (G)