YASKAWA TM.iQp.07 iQpump Controller Programming Manual 111
iQpump MEMOBUS / Modbus Status Registers
The data in these registers is not synchronized to any other MEMOBUS / Modbus register, even if read from within the same “read
multiple” MEMOBUS / Modbus Read Command. This data from various iQpump features is copied and scaled for inclusion in the
following register.
MEMOBUS / Modbus Registers
Table 42 MEMOBUS / Modbus Registers
Register Hex Description
728
Extended Pump Status Word
Bit Description
0 Sleep Active
1 Start Level Delay
2 Thrust Bearing Active
3 Pre-charge Active
4 High Feedback Detected
5 Low Feedback Detected
6 Transducer Loss
7 Setpoint Not Met
8 Loss of Prime
9 Thermostat Fault
A Low Flow Detected
B Utility Delay Active
C Run / Stop Stopped Condition
D Run / Stop Finished (cycles complete)
E Anti-Jam / De-Scale Active
F Reserved
729
Extended Pump Status Word 1
Bit Description
0 Sleep Active
1 Start Level Delay
2 Thrust Bearing Active
3 Pre-charge Active
4 High Feedback Detected
5 Low Feedback Detected
6 Transducer Loss
7 Setpoint Not Met
8 Loss of Prime
9 Thermostat Fault
A Low Flow Detected
B Utility Delay Active
C Run / Stop Stopped Condition
D Run / Stop Finished (Cycles complete)
E Anti-Jam Active
F De-Scale Active