The iQpump drive can be configured to program the drive using units or scaling that are appropriate for the pumping system by
programming the System Units (P1-02). The System Units will affect setpoint references, feedback scaling, pump levels, and display
monitors. The following is a list of parameters that are affected by the programming of the System Units (P1-02).
• d1 Group: d1-01 through d1-04.
• o1 Group: o1-07, o1-08.
• P1 Group: P1-03, P1-04, P1-07, P1-09, P1-11, P1-13.
• P2 Group: P2-02, P2-04, P2-09, P2-10, P2-15, P2-16.
• P3 Group: P3-03, P3-05, P3-07, P3-08, P3-12, P3-14.
• P4 Group: P4-01
• U1 Monitor: U1-91
For further description of each parameter, please refer to the appropriate section or Appendix A.
(*su1) When P1-02 = 13, parameter P1-03 will have to be set to (120 x E1-04 / E2 / 04) for proper display. When P1-02 = 14, parameter
P1-03 will have to be set to the same value as E1-04 for proper display.
<0034>
Table 52 Related Parameters <0034>
◆ P1-03 Feedback Device Scaling
Setting Range: 1 ~ 36000 [based on System Units (P1-02)
Factory Default: 00145 psi
The iQpump drive can be configured to scale the feedback signal using the Feedback Device Scaling Parameter (P1-03). The
programmed value in P1-03 represents the maximum level when a feedback reference is provided to the drive. An example: If a 4-20 mA
signal is provided and P1-03 is set to 145 psi, then 20 mA would represent the maximum psi readout level of 145 psi. This parameter
works in conjunction with the System Units (P1-02).
3 F: Degrees Fahrenheit
4 CFM: Cubic ft / min
5 CMH: Cubic m / hr
6 LPH: Liters / hr
7 LPS: Liters / s
8Bar: Bar
9 Pa: Pascals
10 C: Degrees Celsius
11 ft: Feet
<0032>
12 %: Percent
13 rpm: Revs / min (*su1)
<0034>
14 Hz: Hertz (*su1) <0034>
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description Range Default
Menu
Location
P1-02 601
System Units
System Unit
0: WC: Inch of Water
1: psi: lb / SqrInch
2: GPM: Gallons / min
3: F: DegFarenheit
4: CFM: Cubic ft / min
5: CMH: Cubic m / hr
6: LPH: Liters / hr
7: LPS: Liters / s
8: Bar: Bar
9: Pa: Pascals
10: C: Deg Celsius
11: Mtr: Meters
12:%: Percent
13: rpm: Revs / min (*su 1)
14: Hz: Hertz(*su 1)
0 ~ 14 1 Programming
(*su1) When P1-02 = 13, parameter P1-03 will have to be set to (120 * E1-04 / E2-04) for proper display. When P1-02 = 14, parameter P1-03 will have to be set to the
same value as E1-04 for proper display.
XXXXX