224 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Table 99 Alarm <0034>
Table 100 Message <0034>
Table 101 Multi-Function Output Setting
◆ P7-01 Anti-Jam / De-Scale Operation Selection
◆ P7-02 Anti-Jam / De-Scale Cycle Count
Setting Range: 1 ~ 100
Factory Default: 1
Refer to parameter P7-02 in Appendix A for description details.
◆ P7-03 Anti-Jam Detection Current Level
Setting Range: 50 ~ 200%
Factory Default: 120%
Refer to parameter P7-03 in Appendix A for description details.
◆ P7-04 Anti-Jam Detection Time
Setting Range: 0.1 ~ 2.0 s
Factory Default: 0.3 s
Refer to parameter P7-04 in Appendix A for description details.
◆ P7-05 Anti-Jam / De-Scale Frequency Reference
Setting Range: 0.00 ~ 120.00 Hz
Factory Default: 25.00 Hz
Refer to parameter P7-05 in Appendix A for description details.
oPE16
De-Scale SEt Err
De-Scale Setting Error
A feature incompatible with the De-Scale function is enabled.
Included would be Timed Run, Run / Stop, Multiplex, or 2-motor
alternation.
Reprogram P7-01, b1-02, P4-18 ~
P4-20, P1-01, or P4-14.
Alarm Display Description Cause Countermeasures
Anti-Jam Active During the Anti-Jam function The drive is performing an Anti-Jam function.
Alarm will clear when the
function is complete.
Alarm Display Description Cause Countermeasures
De-Scale Active During the De-Scale function The drive is performing a De-Scale function.
Message will clear when the
function is complete.
Setting Description
53
Anti-Jam / De-Scale
Closed: When the Anti-Jam or the De-Scale features are active (configured by P7-xx)
Setting Description
0Disabled
1Anti-Jam Enabled
2 De-Scale Enabled
3 Force DeScale
Fault Display Description Cause Countermeasures