YASKAWA TM.iQp.07 iQpump Controller Programming Manual 153
Table 59 Parameters
Table 60 Modified Multi-Function Input Setting
Table 61 Multi-Function Input Setting
Table 62 Faults
P1-16 Loss of Prime Time <0034>
Setting Range: 1 - 600 s
Factory Default: 20 s
Prime Loss Time: The “Prime Loss” detection is no longer controlled by parameter P1-12. Instead it is controlled by a new parameter,
P1-16. Also, the “Prime Loss” detection is enabled during the pre-charge function, but only when not ramping (output frequency = pre-
charge frequency).
Parameter P1-16 is used as the “Loss of Prime” fault timer.
Parameter P1-16 should be enabled when in pre-charge, but only when the output frequency is within 1 Hz of the pre-charge frequency.
Loss of Prime Detection is allowed when output frequency is within 1 Hz of d2-01 value instead of the fmax value.
Loss of Prime Detection is allowed regardless of how many pumps are staged (contactor multiplex operation).
Loss of Prime is enabled during Timed Run and Run / Stop Control.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator Display
Description Range Default
Menu
Location
P1-15 10A
Low / Hi Water Digital Input
Configuration
Water DI Config
0 = Low N.O.-Hi N.O. (Low Water Normally Open High Water
Normally Open)
1 = Low N.C.-Hi N.O. (Low Water Normally Closed High Water
Normally Open)
2 = Low N.O.-Hi N.C. (Low Water Normally Open High Water
Normally Closed)3
3 = Low N.C.-Hi N.C. (Low Water Normally Closed High Water
Normally Closed)
0 ~ 3 0 Programming
Setting Description
85
Low Water Level
Function Active in Auto Mode during normal operation, also used with pre-charge function.
Function logic depends on parameter P1-15 (Water DI Config)
P1-15 = 0 or 2 (Normally Open)
Closed: Low Water Level Fault
Open: Reservoir / Tank is filled to normal level
P1-15 = 1 or 3 (Normally Closed)
Closed: Reservoir / Tank is filled to normal level
Open: Low Water Level Fault
Pre-charge function: Function uses low water level input as “Tank / Reservoir” feedback to indicate water level reached. Important: Program
P1-15 to 0 or 2 when the “Low Water” function is not used.
Setting Description
76
High Water Level
Function will be active whenever the drive is running.
Function logic depends on parameter P1-15 (Water DI Config)
P1-15 = 0 or 1 (Normally Open)
Closed: High Water Level Fault
Open: Reservoir / Tank is filled to normal level
P1-15 = 2 or 3 (Normally Closed)
Closed: Reservoir / Tank is filled to normal level
Open: High Water Level Fault
Fault Display Description Cause Countermeasures
High FB / High Water
HFB / HW
High Feedback Fault -
Feedback signal is too high.
OR
The “High Water Level” digital
input is active (H1-0x = 88).
The feedback level has risen above P1-09 level for the
time specified in P1-10. High feedback fault is active
in Hand Mode, Auto Mode, Pre-charge and Thrust
Mode when the drive is running.
OR
High Water Level Switch is activated / defective or P1-
15 is programmed incorrectly.
Feedback level lower than P1-09 High Feedback
Level.
OR
Lower the water level / adjust the High Water Level
switch.
High FB /Water
HFB/HW
0.00 Hz
0.00 A
U2-04 =
U2-05 =