YASKAWA TM.iQp.07 iQpump Controller Programming Manual 103
MEMOBUS / Modbus Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.
■ Reference Data
The reference data table is shown below. Reference data can be read and written to.
Table 37 Reference Data
Register Hex Contents
0000 Reserved
0001
Sequence Control
Bit 0 Run Forward 1: Run 0: Stop
Bit 1 Run Reverse 1: Run 0: Stop
Bit 2 External fault1: Fault (EFO)
Bit 3 Fault reset1: Reset command
Bit 4 ComNet
Bit 5 ComCtrl
Bit 6 Multi-function digital input command 3
Bit 7 Multi-function digital input command 4
Bit 8 Multi-function digital input command 5
Bit 9 Multi-function digital input command 6
Bit A Multi-function digital input command 7
Bits B ~ F Not used
0002 Frequency reference (Set units using parameter o1-03)
0003 ~ 0005 Not used
0006 PI Setpoint
0007 Analog output 1 setting (-11 V = 726 ~ 11 V = 726) → 10 V = 660
0008 Analog output 2 setting (-11 V = 726 ~ 11 V = 726) → 10 V = 660
0009
Multi-function contact output setting
Bit 0 Digital output 1 (Terminal M1-M2) 1: ON 0: OFF
Bit 1 Digital output 2 (Terminal M3-M4) 1: ON 0: OFF
Bit 2 Not Used
Bits 3 ~ 5 Not used
Bit 6 Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7 Fault contact (terminal MA-MC) 1: ON 0: OFF
Bits 8 ~ F Not used
000A ~ 000E Not used
000F
Reference selection settings
Bit 0 Not used
Bit 1 Input PI Setpoint 1: Enabled 0: Disabled
Bits 3 ~ B Not used
C Broadcast data terminal S5 input 1: Enabled 0: Disabled
D Broadcast data terminal S6 input 1: Enabled 0: Disabled
E Broadcast data terminal S7 input 1: Enabled 0: Disabled
F Not used
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.