Table 2 480 VAC Drives
Drive Model
CIMR-P7U-
-107
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
40P4 0.5/0.75 576.40 1.0 0.6 38.198 0.1 0.1 0.3 95 °C5
40P7 1 447.40 1.6 0.8 22.459 0.1 0.2 0.3 95
°C7.5
41P5 1.5/2 338.80 3.1 1.4 10.100 0.2 0.3 0.3 95
°C10
42P2 3 313.60 4.2 1.5 6.495 0.3 0.4 0.3 90
°C10
43P7 5 245.80 7.0 2.3 3.333 0.5 0.5 0.3 95
°C12
45P5 7.5 189.50 13.3 2.6 1.595 1.0 0.6 0.3 95
°C10
47P5 10 145.38 19.9 4.0 1.152 1.0 0.7 0.3 90
°C20
49P0 15 145.46 21.0 4.4 0.922 1.0 0.8 0.3 95
°C23
4011 15/20 140.88 26.5 5.6 0.922 2.0 0.8 0.3 95
°C23
4015 25 126.26 32.9 7.6 0.550 2.0 0.9 0.3 95
°C17
4018 30 115.74 52.3 7.8 0.403 2.0 1.0 0.6 98
°C17
4024 40 89.08 52.0 8.6 0.269 2.0 1.1 0.6 85
°C20
4030 40/50 92.54 65.6 10.9 0.269 2.0 1.1 0.6 85
°C20
4037 60 76.32 79.7 19.1 0.155 2.0 1.1 0.6 85
°C20
4045 75 71.56 95.0 22.0 0.122 2.0 1.2 0.6 90
°C20
4055 100 67.20 130.0 24.0 0.088 2.0 1.2 1.0 90
°C20
4075 125 46.20 130.0 36.0 0.092 2.0 1.3 1.0 98
°C16
4090 150 38.91 156.0 40.0 0.056 2.0 1.5 1.0 108
°C16
4110 200 36.23 190.0 49.0 0.046 2.0 1.7 1.0 100
°C16
4160 250 30.13 270.0 70.0 0.029 2.0 1.8 1.0 108
°C14
4185 300/350 30.57 310.0 81.0 0.025 2.0 0.7 1.0 95
°C15
4220 400/450 27.13 370.0 96.0 0.020 2.0 0.8 1.0 100
°C15
4300 500+ 21.76 500.0 130.0 0.014 2.1 0.9 1.0 95
°C15
Note: b8-04 = Energy Savings Coefficient
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level