YASKAWA TM.iQp.07 iQpump Controller Programming Manual 87
H3-08 Terminal A2 Signal Level
The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2 analog input.
The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The iQpump drive also has a DIP switch (S1) on the
removable terminal board that must be set for the proper reference signal into the A2 analog input. The S1-2 dipswitch setting determines
the internal resistance of the A2 input while parameter H3-08 determines how the iQpump drive interprets the measured signal.
Figure 1.76
Figure 1.77
Figure 76. DIP Switch S1
Table 32 DIP Switch S1
Setting Description
0 0 - 10 Vdc
2 4 - 20 mA (factory default)
3 0 - 20 mA
Name Function Setting
S1-1 RS-485 and RS-422 terminating resistance
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
S1-2 Input method for analog input A2
OFF: 0 to 10 V (internal resistance: 20 kΩ)
ON: 4 ~ 20 mA (internal resistance: 250 Ω) (Default)
S1
O
1
Terminating
resistance
DIP Switch S1-1 located on
terminal board.
2
1