282 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
P3-02
0615
Drive Multi / Maximum
Level
Max-Multi Level
Sets the maximum level used for multiplex pumping operation.
Parameter is active when P3-01 = 0 or P3-01 = 2 is selected.
P3-01 = 0: When the output frequency rises above the level
programmed in P3-02 for a time specified in P3-04, the next available
pump will be added to the system by means of a multi-function digital
output closure (H2-XX = 40, 41).
P3-01 = 1: Not Used.
P3-01 = 2: When the output frequency rises above level programmed
in P3-02 and the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure (H2-XX = 40, 41).
0.0 ~
120.00 Hz
59.0 Hz Programming
178
P3-03
0616
Add Pump Delta Level
Add Pump D-Lvl
Sets the level used for multiplex pumping operation. The parameter is
active when P3-01 =1 or P3-01 = 2 is selected.
P3-01 = 0: Not Used
P3-01 = 1: When the delta feedback (setpoint minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).
P3-01 = 2: When the output frequency rises above level programmed
in P3-02 and the delta feedback (Set-point minus feedback) has
exceeded the level programmed in P3-03 for a time specified in P3-04,
the next available pump will be added to the system by means of a
multi-function digital output closure. (H2-XX = 40, 41).
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 ~
6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
179
P3-04
0617
Add Pump Delay Time
Add Pump Dly Tm
Sets the delay time before a pump is added to the system. Works in
conjunction with parameters P3-02, P3-03, and P2-11 to P2-19.
0 ~ 3600 s 2 s Programming
179
P3-05
0618
Shutdown Pump Delta
Level
Shdn Pump D-Lvl
Sets the level used for multiplex pumping operation. Parameter is
active when P3-01 = 1 or P3-01 = 2 is selected.
P3-01 = 0: Not Used
P3-01 =1 : When the delta feedback (feedback minus setpoint) has
exceeded the level programmed in P3-05 for a time specified in
P3-06,the last pump that was brought online will be shutdown by
means of a multi-function digital output opening. (H2-XX = 40, 41).
P3-01 = 2: When the output frequency drops below level programmed
in P3-09 or P3-10 (depends on last pump running) and the delta
feedback (feedback minus setpoint) has exceeded the level
programmed in P3-05 for a time specified in P3-06, the last pump that
was brought online will be shutdown by means of a multi-function
digital output opening. (H2-XX = 40, 41).
Note: Do not program this level too close to the system setpoint or
excessive cycling of the pump system may occur.
0.0 ~
6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
179
P3-06
0619
Shutdown Pump Delay
Time
Shdn Pump Dly Tm
Sets the delay time before one of the additional across the line pumps is
shutdown.Works in conjunction with parameters P3-02 and P3-03.
0 ~ 3600 s 5 s Programming
180
P3-07
061A
Multi Pump Set-point
Increase
MP Set-point Incr
Sets the amount the drive’s setpoint will decrease for each time a new
pump is brought offline.
Pump 1: Set-point
Pump 1+2: Set-point + P3-07
Pump 1+2+3: Set-point + (2 x P3-07)
0.0 ~
6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
180
P3-08
061B
Multi Pump Set-point
Decrease
MP Set-point Decr
Sets the amount the drive’s setpoint will increase for each time a new
pump is brought online.
Pump 1: Set-point
Pump 1+2: Set-point - P3-08
Pump 1+2+3: Set-point - (2 x P3-08)
0.0 ~
6000.0
(system
units
P1-02)
0.0
(system
units
P1-02)
Programming
181
Denotes that parameter can be changed when the drive is running.
Parameter
No.
Addr.
Hex
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.