298 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Factory Default Settings
The following tables detail the factory default settings for the parameters that are affected by the setting of parameter o2-04.
Table 1 208/240 VAC Drives
Drive Model
CIMR-P7U-
-107
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
20P4 0.5/0.75 288.2 1.9 1.2 9.842 0.1 0.1 0.3 95 °C5
20P7 2 223.7 3.3 1.8 5.156 0.1 0.2 0.3 95
°C7.5
21P5 1.5/2 169.4 6.2 2.8 1.997 0.2 0.3 0.3 95
°C10
22P2 3 156.8 8.5 3.0 1.601 0.3 0.4 0.3 100
°C12
23P7 5 122.9 14.0 4.5 0.771 0.5 0.5 0.3 95
°C12
25P5 7.5 94.75 19.6 5.1 0.399 1.0 0.6 0.3 95
°C10
27P5 10 72.69 26.6 8.0 0.288 1.0 0.7 0.3 95
°C17
2011 15 70.44 39.7 11.2 0.230 1.0 0.8 0.3 95
°C21
2015 20 63.13 53.0 15.2 0.138 2.0 0.9 0.3 90
°C17
2018 25 57.87 65.8 15.7 0.101 2.0 1.0 0.6 100
°C15
2022 30 51.79 77.2 18.5 0.079 2.0 1.0 0.6 90
°C24
2030 40 46.27 105.0 21.9 0.064 2.0 1.1 0.6 90
°C20
2037 50 38.16 131.0 38.2 0.039 2.0 1.1 0.6 95
°C18
2045 60 35.78 160.0 44.0 0.030 2.0 1.2 0.6 100
°C20
2055 75 31.35 190.0 45.6 0.022 2.0 1.2 0.1 105
°C17
2075 75/100 23.10 260.0 72.0 0.023 2.0 1.3 0.1 110
°C16
2090 125 20.65 260.0 72.0 0.023 2.0 1.5 0.1 100
°C18
2110 150 18.12 260.0 72.0 0.023 2.0 1.7 0.1 95
°C20
Note: b8-04 = Energy Savings Coefficient
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level