86 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Adjustment of the bias setting will likewise adjust the speed command that is equivalent to the minimum analog input level (0 Vdc or 4
mA). If, for instance, the bias is set to –25%, then 0 Vdc or 4 mA will be equivalent to a –25% speed command. Since the minimum
speed command is 0% an analog input of 2 to 10 Vdc or 7.2 to 20 mA will now be equivalent to 0-100% speed command span.
Figure 1.74
Figure 74. Output Frequency with Reduced Bias Setting
As a further example, for an inverse-acting speed command, set the bias = 100% and the gain = 0%. The minimum analog input level (0
Vdc or 4 mA) will produce a 100% speed command and the maximum analog input level (10 Vdc or 20 mA) will produce a 0% speed
command.
Figure 1.75
Figure 75. Output Frequency with Inverted Gain and Bias Settings
2 V
7.2 mA
Analog Input Signal
Frequency
Analog Input Signal
Bias
Gain
Commentaires sur ces manuels