216 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
Table 93 Multi-Function Output Settings (H2-xx) <0034>
Table 94 Faults <0034>
Table 95 Alarms <0034>
P6-02 Water Flow Units
Setting Range: 0 ~ 4
Factory Default: 0
P6-03 Flow Accumulation Reset
Setting Range: 0 ~ 65535
Factory Default: 0
Refer to parameter P6-03 in Appendix A for description details.
Setting Description
4E
Low Flow
Closed: During the “Low Flow Fault” condition OR
Closed: During a low flow condition as set by P6-04 ~ P6-06 (includes “Low Flow Alarm”).
4F
<2>
Accum Level
<2>
Closed: Accumulated level has exceeded the P6-09 and P6-10 setting OR
Closed: During the “Accum Level” Fault.
56
<3>
High Flow
<3>
Closed: During the “High Flow Fault” condition OR
Closed: During a high flow condition as set by P6-04 ~ P6-06 (includes “High Flow Alarm”)
Fault Display Description Cause Countermeasures
LOWFL
Low Flow
Low flow has been detected by the flow
meter.
Not enough flow, or incorrect “P6” settings
ACCUM
Accum Level
Accumulated Level Accumulated level has exceeded the P6-09 and P6-10 settings.
Reset the accumulated level
(P6-03 or via digital input)
OPE13
Terminal A1
Programming error
Terminal A1 is being assigned to more than one of the following
functions.
- Frequency Reference (b1-01 = 1)
- Dual Zone PI is enabled (b5-01 = 2)
- Flow Meter Enabled (P6-01 > 0)
- Level Control Enabled (P8-01 =1)
Reprogram b1-01, b5-01, P6-01
or P8-01.
OPE14
FlowMtrNotEnable
Programming error
The sleep level type has been set to “FlowMtr-Term A1”
(P2-01 = 4) but the flow meter function is not enabled
(P6-01 = 0.0)
Reprogram P2-01 or P6-01.
HIFLO
High Flow
High flow has been detected by the flow
meter.
Too much flow or incorrect “P6” settings.
Alarm Display Description Cause Countermeasures
LOWFL
Low Flow
Low flow has been detected by the flow
meter.
Not enough flow, or incorrect “P6” settings
ACCUM
Accum Level
Accumulated Level Accumulated level has exceeded the P6-09 and P6-10 settings.
Reset the accumulated level
(P6-03 or via digital input)
HIFLO
High Flow
High flow has been detected by the flow
meter.
Too much flow or incorrect “P6” settings.
Setting Description
0 U.S. Gallons / min (GPM)
1 U.S. Gallons / hr (GPH)
2 U.S. Barrels / min (BPM)
3 U.S. Barrels / hr (BPH)
4 U.S. Barrels / Day (BPD)