226 YASKAWA TM.iQp.07 iQpump Controller Programming Manual
P8 Pressure and Level Control <0034>
For Quick Set-up procedures refer to TM.iQp.06 iQpump Drive User Manual, Appendix G.
P8-01 Pressure and Level Control Select
Setting Range: 0 ~ 1
Factory Default: 0
Controls the Constant Pressure With Well Draw Down Control.
0: Disabled
1: Enabled
Overview
This parameter will allow the drive to control pressure when there is adequate water inside of the well. When the well level drops to the
Water Level Setpoint (P8-03), it will regulate the well level and the pressure will be allowed to drop. The drive will also go to sleep, wake
up, and / or alarm / fault based on well water level.
Figure 1.170
Figure 174. System Overview
A2 - PI Fdbk.
A1 - Well Depth Fdbk.
Analog 4-20 mA
Pressure Sensor
Analog 4-20 mA
Liquid
Output
T1 T2 T3
P8-05 Wake-Up Level
P8-03 Water Level Setpoint
P8-04 Minimum Water level
P8-07 Water Alarm/Fault Level
Pump
Well Depth Sensor