YASKAWA TM.iQp.07 iQpump Controller Programming Manual 53
E1-04 Maximum Output Frequency
Setting Range: 0.0 ~ 120.0 Hz
Factory Default: 60.0 Hz
Refer to parameter E1-04 in Appendix A for description details.
E1-05 Maximum Output Voltage
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
0.0 ~ 510.0 V (480 V Models)
Factory Defaults: 240.0 V (240 V Models)
480.0 V (480 V Models)
Refer to parameter E1-05 in Appendix A for description details.
E1-06 Base Frequency
Setting Range: 0.0 ~ 120.0 Hz
Factory Default: 60.0 Hz
Refer to parameter E1-06 in Appendix A for description details.
E1-07 Mid Output Frequency A
Setting Range: 0.0 ~ 120.0 Hz
Factory Default: 3.0 Hz
Refer to parameter E1-07 in Appendix A for description details.
E1-08 Mid Output Voltage A
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
0.0 ~ 510.0 V (480 V Models)
Factory Defaults: 17.2 V (240 V Models)
34.5 V (480 V Models)
Refer to parameter E1-08 in Appendix A for description details.
E1-09 Minimum Output Frequency
Setting Range: 0.0 to 120.0 Hz
Factory Default: 1.5 Hz
Refer to parameter E1-09in Appendix A for description details.
E1-10 Mid Output Voltage
Setting Ranges: 0.0 ~ 255.0 V (240 V Models)
0.0 ~ 510.0 V (480 V Models)
Factory Defaults: 10.3 V (240 V Models)
20.7 V (480 V Models)
Refer to parameter E1-10 in Appendix A for description details.