
YASKAWA TM.iQp.07 iQpump Controller Programming Manual 31
b4 Delay Timers
The iQpump drive has an internal timer function that operates independently from the drive. A digital input must be programmed to be a
timer start input by setting H1-0x = 18. A digital output must be programmed as a timer output by setting H2-0x = 12. (Not to be
confused with the “Wait to Run Time” in b1-11.)
◆ b4-01 Timer Function ON-Delay Time
Setting Range: 0.0 ~ 3000.0 s
Factory Default: 0.0 s
The timer start input (H1-0x = 18) must be held on for at least the time specified in parameter b4-01 before the digital output programmed
as the timer output will close. See Figure 25. for timing details.
◆ b4-02 Timer Function OFF-Delay Time
Setting Range: 0.0 ~ 3000.0 s
Factory Default: 0.0 s
The timer start input (H1-0x = 18) must be held off for at least the time specified by b4-02 before the digital output programmed as the
timer output will open. See Figure 25. for timing details.
Figure 1.25
Figure 25. Timing Diagram of Timer Function
Multi-function Contact
Input: Timer Function
Multi-function Contact
Output: Timer Function
b4-01
b4-01
b4-02
ON (CLOSED)
OFF (OPEN)
ON (CLOSED
OFF (OPEN)
b4-02
Commentaires sur ces manuels