Yaskawa iQpump Controller Programming Manual Manuel d'utilisateur Page 239

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 302
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 238
YASKAWA TM.iQp.07 iQpump Controller Programming Manual 239
Table 116 Monitors
Monitor shown only when P1-01 = 3 (MEMOBUS / Modbus Network)
P9-05 Lag Drive Mode
P9-06 Lag Fixed Speed
Setting Range: 0.00 ~ 120.00 Hz
Factory Default: 55.00 Hz
Refer to parameter P9-06 in Appendix A for description details.
P9-07 Lag Fixed Speed Delay
Setting Range: 0.0 ~ 1000 s
Factory Default: 5 s
Refer to parameter P9-07 in Appendix A for description details.
P9-08 Add Pump Mode
P9-09 Add Freq Level
Setting Range: 0.0 ~ 120.0 Hz
Factory Default: 56.0 Hz
Refer to parameter P9-09 in Appendix A for description details.
P9-10 Add Delta Level
Setting Range: 0 ~ 6000.0
Factory Default: 5.0
Refer to parameter P9-10 in Appendix A for description details.
P9-11 Add Delay Time
Setting Range: 0 ~ 3600 s
Factory Default: 10 s
Refer to parameter P9-11 in Appendix A for description details.
Monitor
No.
Addr.
Hex
Monitor Name
Digital Operator Display
Description
U1-68 0009C
Time to Alternate
Time to Alternate
Time remaining before a drive requests alternation which is dependent on P9-04.
Setting Description
0 Fixed Speed - Runs at the P9-06 setting.
1 PI Regulation - Uses PI to determine speed.
Setting Description
0 Output Frequency
1 Feedback
2 Feedback + Fout
Vue de la page 238
1 2 ... 234 235 236 237 238 239 240 241 242 243 244 ... 301 302

Commentaires sur ces manuels

Pas de commentaire