Yaskawa iQpump Controller Programming Manual Manuel d'utilisateur Page 201

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 302
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 200
YASKAWA TM.iQp.07 iQpump Controller Programming Manual 201
Table 76 Alarms <0034>
Table 77 Multi-Function Output Setting <0034>
P4-12 Pre-charge Frequency 2 <0034>
Setting Range: 0 ~ 120.00 Hz
Factory Default: 0.00 Hz
Refer to parameter P4-12 in Appendix A for description details.
P4-13 Pre-charge Time 2 <0034>
Setting Range: 0 ~ 3600.0 min
Factory Default: 0.0 min
Refer to parameter P4-13 in Appendix A for description details.
P4-14 Two Motor Alternation Selection <0034>
This parameter allows one drive to power two motors in an “OR” configuration to keep the amount of wear on each motor / pump
balanced. This feature will utilize one digital output, which will drive two output contactors via a form-C pilot relay. This feature is only
available in Simplex mode (P1-01 = 0).
Alarm Display Description Cause Countermeasures
Utility Delay Adjust by
P4-11
Utility Delay
This message will appear when the drive is delaying
the run command due to the Utility Start Delay
Function.
Wait until the P4-11 time to elapse, or cycle the run
command.
Setting Description
50
Utility Delay
Closed: Drive is stopped and is waiting for the utility delay timer to expire. (configured by P4-11)
Setting Description
0Disabled
1 Enabled
2 Motor 1 Only
3 Motor 2 Only
Vue de la page 200
1 2 ... 196 197 198 199 200 201 202 203 204 205 206 ... 301 302

Commentaires sur ces manuels

Pas de commentaire